| 2014-11-03 12:55:22 | TO JG'S DESK. |
| | |
| | |
| 2014-11-03 12:14:23 | DATE: 11/3/2014 |
| | PROJECT: BARCELONA RD RENNOVATION |
| | PERMIT#: 14080856 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 3RD ELECTRICAL PLAN REVIEW |
| | ACTION: PROVISO |
| | |
| | 1) INDICATE THE LOCATION FOR THE ELECTRICAL PANELS. |
| | 2010 WPB AMENDMENTS TO THE FBC107.3.5 |
| | |
| | 2) REVISE PANEL SCHEDULE "A" TO CORRECT PROBABLE TYPO |
| | FOR "KITCHEN" CIRCUIT #23 INDICATING A SINGLE POLE |
| | 60AMP OCPD WITH #6 WIRE. |
| | WHICH 110V 1POLE CIRCUIT IS IDENTIFIED AS "KITCHEN"? |
| | PLEASE CLARIFY BY INDICATING CIRCUIT NUMBERS ON THE |
| | FLOOR PLAN TO CORRESPOND TO CIRCUIT NUMBERS ON THE |
| | PANEL SCHEDULES. |
| | |
| | 3) REVISE THE RISER DIAGRAM AN VERIFY THE METAL NATURAL |
| | GAS PIPING BE BONDED IN ACCORDANCE WITH THE NEC |
| | 250.104(B) |
| | |
| | 4) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. NEC 110.9 |
| | |
| | 5) VERIFY LUMINAIRES AND EXHAUST FANS LOCATED IN THE |
| | BATHROOMS OVER BATHTUB OR SHOWER SHALL BE IN ACCORDANCE |
| | WITH THE NEC 410.10(D) BATHTUB AND SHOWER, AND |
| | NEC110.3(B) LISTING AND LABELING |
| | |
| | 6) VERIFY ALL RECEPTACLE OUTLETS INSTALLED THROUGHOUT |
| | THE HOUSE SHALL BE INSTALLED IN COMPLIANCE WITH NEC |
| | 210.52(A)(1) SHALL BE INSTALLED SUCH THAT NO POINT |
| | MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL |
| | SPACE IS MORE THAN (6 FT) FROM A RECEPTACLE OUTLET. |
| | |
| | 7) A GFI OUTLET SHALL BE INSTALLED AT EACH COUNTERTOP |
| | SPACE THAT IS 12" OR WIDER. GFI OUTLETS SHALL BE |
| | INSTALLED SO THAT NO POINT ALONG THE WALL LINE IS MORE |
| | THAN 24" HORIZONTALLY FROM AN OUTLET IN THAT SPACE. NEC |
| | 210.52(C)(1). THERE APPEAR TO BE ADDITIONAL OUTLETS |
| | REQUIRED AT COUNTERTOP WALL SPACE AREAS IN THE KITCHEN. |
| | |
| | 8) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES |
| | INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) |
| | SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION |
| | FOR PERSONNEL. ALL OUTLETS IN THE KITCHEN, BATHROOM, |
| | OUTDOORS, LAUNDRY, UTILITY, AND WET BAR SINKS SHALL BE |
| | GFCI PROTECTED. NEC 210.8. |
| | |
| | 9) METAL FRAMING MEMBERS SHALL BE BONDED TO THE |
| | EQUIPMENT GROUNDING CONDUCTOR FOR THE CIRCUIT THAT MAY |
| | ENERGIZE THE FRAMING AND BE SIZED IN ACCORDANCE WITH |
| | THE NEC TABLE 250.122. FOR THE PURPOSE OF THIS SECTION, |
| | A GROUNDED METAL OUTLET BOX ATTACHED TO THE FRAMING |
| | SHALL BE PERMITTED. FBC 2704 |
| | |
| | SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR SECURITY, CCTV, STUCTURED CABLING, |
| | NETWORK, AUDIO/VIDEO, GENERATOR, SWIMMING POOL, |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |