| 2014-10-09 10:21:39 | DATE: 10/21/2014 |
| | PROJECT: BARCELONA RD RENNOVATION |
| | PERMIT#: 14080856 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) REVISE THE RISER DIAGRAM TO INDICATE A LOGICAL |
| | DESIGN UTILIZING FULL SIZE SERVICE ENTRANCE CONDUCTORS |
| | FEEDING PANELS "A" AND "B" NEC 310.15.(B)(6) . |
| | |
| | 2) REVISE THE RISER DIAGRAM TO INCLUDE AN EQUIPMENT |
| | GROUNDING CONDUCTOR IN THE FEEDER TO THE GARAGE PANEL. |
| | NEC 250.122 |
| | |
| | 3) REVISE THE PANEL "A" SCHEDULE TO TO CORRECT PROBABLE |
| | TYPO FOR KITCHEN CIRCUIT #23 INDICATING A 60AMP OCPD |
| | WITH #12 WIRE. |
| | |
| | 4) CLARIFY THE TYPE, RATING, SIZE AND USE FOR THE |
| | GUTTER INDICATED ABOVE PANELS "A" AND "B" ON THE RISER |
| | DIAGRAM. WPB AMENDMENTS TO THE FBC 107.3.2 |
| | |
| | 5) VERIFY LUMINAIRES IN CLOTHES CLOSETS SHALL BE |
| | INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF THE NEC |
| | 410.16(A) AND (B). |
| | |
| | 6) VERIFY ALL RECEPACLE OUTLETS INSTALLED THROUGHOUT |
| | SHALL BE IN COMPLIANCE WITH NEC 210.52(A)(1) SHALL BE |
| | INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| | ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 1.8 |
| | M (6 FT) FROM A RECEPTACLE OUTLET. |
| | |
| | 7) INDICATE THE REQUIRED WORKING CLEARANCES FOR THE A/C |
| | DISCONNECTS. SEE NEC 110.26 |
| | SUFFICIENT ACCESS AND WORKING SPACE SHALL BE PROVIDED |
| | AND MAINTAINED ABOUT ALL ELECTRICAL EQUIPMENT TO PERMIT |
| | READY AND SAFE OPERATION AND MAINTENANCE OF SUCH |
| | EQUIPMENT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |