| 2014-09-11 19:00:07 | RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- BOTH SET OF PLANS SUBMITTED NEED TO BE SIGNED AND |
| | SEALED BY THE ARCHITECT OF RECORD AS REQUIRED BY |
| | CHAPTER 481 FLORIDA STATUTES. |
| | ***NOTE: MAKE SURE BOTH SETS ARE THE SAME. ONE SET |
| | SUBMITTED WAS DATED 05/15/2014 AND THE OTHER ONE WAS |
| | DATED 07/01/2014. COORDINATE THE DRAWINGS BEFORE |
| | RE-SUBMITTAL TO AVOID CONFLICTS AND DELAYS. |
| | |
| | 2- BRING PLANS TO PALM BEACH COUNTY TO VERIFY IF IMPACT |
| | FEES ARE DUE. BRING BACK COUNTY STAMPED PLANS AND COPY |
| | OF PAID RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY |
| | IMPACT FEE ORDINANCE OF THE LAND DEVELOPMENT CODE. |
| | |
| | 3- SHEET SP-1: |
| | A) NOTE REGARDING THE EXISTING BUILDING ALTERATION |
| | LEVEL IS INCOMPLETE. COMPLETE THE ALTERATION LEVEL |
| | INFORMATION AND ALSO KEEP IN MIND THAT THIS IS AN |
| | ADDITION ALSO. SEC. 401.4 OF 2010 FBC-EXISTING BUILDING |
| | |
| | B) FIRE DEPARTMENT NOTES AND REFERENCED CODE SECTIONS |
| | DON'T APPLY TO SINGLE FAMILY RESIDENCES. THESE NOTES |
| | ARE NOT NEED IT. REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 4- NEW MASTER BEDROOM EGRESS WINDOWS: PROVIDE |
| | MANUFACTURERS CUT SHEETS SHOWING SIZES SPECIFIED IN |
| | PLANS TO VERIFY COMPLIANCE WITH THE EGRESS REQUIREMENTS |
| | OF SEC. R310 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 5- PROVIDE ICYNENE EVALUATION REPORT TO SHOW COMPLIANCE |
| | WITH SEC. R316. |
| | |
| | 6- SHEET S4: |
| | A) PROVIDE COMPLETE SPECIFICATIONS FOR THE TYPE OF |
| | SECOND FLOOR SHEATHING AND ROOF SHEATHING. THERE IS NO |
| | INFORMATION ON PLANS. SEC. R301 OF 2010 |
| | FBC-RESIDENTIAL. |
| | |
| | B) ROOF SHEATHING NAILS NEED TO BE RING SHANK NAILS AS |
| | REQUIRED BY SEC. R803.2.3.1 OF 2010 FBC-RESIDENTIAL. |
| | CLEARLY INDICATE THAT NAILS NEED TO BE RING SHANK |
| | NAILS. |
| | |
| | 7- A) DESIGN PROFESSIONAL TO CLEARLY SPECIFY ON PLANS |
| | TYPE OF ROOFING SYSTEM, MATERIALS AND FASTENING AS |
| | REQUIRED BY SEC. 107.2.1.2 OF CITY AMENDMENTS TO FBC. |
| | (NOTE: IF USING FOAM ADHESIVE FOR TILE INSTALLATION, |
| | THEN, CLEARLY IDENTIFY ON TABLE 3A-2 OF FLORIDA PRODUCT |
| | APPROVAL FL7804-R7 SUBMITTED WHICH ADHESIVE IS GOING TO |
| | BE USED TO VERIFY COMPLIANCE WITH THE ATTACHMENT |
| | RESISTANCE). |
| | |
| | B) PRODUCT APPROVAL FL14317-R5 ROOFING UNDERLAYMENT |
| | SUBMITTED MAY NOT BE USED. DESIGN PRESSURES SHOWN ON |
| | LIMITATION 5.5.2 THRU 5.5.2.3 DON'T MEET THE REQUIRED |
| | DESIGN PRESSURES OF SEC. R301. NEED TO USE ANOTHER |
| | PRODUCT. AND, COORDINATE WITH ITEMS #6(C) AND #7(A) |
| | ABOVE. |
| | |
| | C) PRODUCT APPROVAL FL11915-R3 SUBMITTED. CLEARLY |
| | SPECIFY WHICH SPECIFIC UNDERLAYMENT IS GOING TO BE |
| | USED. COORDINATE WITH DESIGN PROFESSIONAL |
| | SPECIFICATIONS REQUIRED BY ITEM # 7(A) ABOVE. |
| | |
| | 8- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| | FOR THE INSTALLATION OF THE ROUND WINDOW AS SPECIFIED |
| | ON PLANS. SEC. R612.10.2 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 9- PROVIDE PROVIDE PRODUCT APPROVAL (2 COPIES) AS |
| | REQUIRED BY DCA RULE 9N-3 FOR: |
| | A) ROOF TILE UNDERLAYMENT IF USING SELF ADHERING |
| | UNDERLAYMENT. FLORIDA PRODUCT APPROVAL FL14317-R5 |
| | SUBMITTED CAN'T BE USED. SEE ITEM #7(B) ABOVE. |
| | |
| | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON ALL |
| | DETAILS/ SECTIONS AND SPECIFICATIONS. (NOTE: PROVIDE |
| | ONLY THE PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING |
| | THE CONNECTOR OR WRITE DOWN THE PRODUCT APPROVAL NUMBER |
| | NEXT TO THE SPECIFIED STRUCTURAL CONNECTORS IN ALL |
| | DETAILS). |
| | |
| | 10- DESIGN PROFESSIONAL OF RECORD TO REVIEW AND APPROVE |
| | IN WRITING (NOT SIGNING AND SEALING) ALL PRODUCT |
| | APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS |
| | TO FBC. |
| | |
| | ***NOTES: |
| | *** PROVIDE RESPONSE LETTER ADDRESSING EACH COMMENT TO |
| | EXPEDITE THE REVIEW PROCESS. |
| | *** PLEASE REMOVE AND REPLACE ANY REVISED SHEET WHEN |
| | RE-SUBMITTING TO EXPEDITE THE REVIEW PROCESS. |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | (561)805-6712 |
| | [email protected] |