Plan Review Notes
Plan Review Notes For Permit 14080406
Permit Number 14080406
Review Stop B
Sequence Number 2
Notes
Date Text
2014-11-26 15:25:112ND REVIEW: FBC 2010
  
 THERE IS A SIMILAR EXISTING ALUMINUM STRUCTURE ATTACHED
 TO A BUILDING ON THIS PROPERTY TO THE N OF THE PROPOSED
 IMPROVEMENT. THERE DOES NOT APPEAR TO BE A PERMIT
 RECORD FOR THIS STRUCTURE. PLEASE PROVIDE EVIDENCE OF
 THIS PERMIT.
  
 THE PRODUCT APPROVAL SUBMITTED (FL 7621-R2) HAS NO
 EVIDENCE OF REVIEW BY TIMOTHYJ. MESSLER, PE, ENGINEER
 OF RECORD. ADDITIONALLY, THIS PRODUCT IS FOR PANELS OF
 4" OR 6" THICKNESS. THE MESSLER DRAWING SPECIFYS PANELS
 OF 3" THICKNESS. PLEASE CLARIFY.
  
 THE ROOF PANEL SPAN IS SHOWN AS 9'10" ON SHEET 2 AND
 12'0" ON SHEET 3. PLEASE CLARIFY.
  
 DETAIL A, SHEET 3 SHOWS AN ALUMINUM I BEAM AS EXISTING.
 THIS DOES NOT APPEAR TO BE ACCURATE. PLEASE VERIFY.
  
 GENERAL NOTES COVER SHEET INDICATES A DESIGN PRESSURE
 OF -67 PSF WHICH EXCEEDS ANY MAXIMUM ALLOWABLE PRESSURE
 OF THE ROOFING PANEL. ADDITIONALLY, EXPOSURE B IS
 CLAIMED BUT THE EXISTANCE OF A BASEBALL PARK TO THE
 EAST OF THE PROPERTY RESULTS IN AN EXPOSURE C. SEE THE
 ROOFING PANEL INSTRUCTIONS FOR SITE SPECIFIC REQUIRED
 DESIGN WIND PRESSURES.
  
 EXISTING BUILDING DATA ON SHEET 3 INDICATES THE TYPE OF
 CONSTRUCTION AS IIB AND THAT THE PROPOSED IMPROVEMENT
 IS ALSO TYPE IIB. THE ROOF PANELS ARE NOT OF NON
 COMBUSTIBLE CONSTRUCTION AS REQUIRED FOR IIB. CONSIDER
 RECLASSIFYING THE STRUCTURE PER TABLE 503
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER