| Plan Review Notes For Permit 14080395 |
| Permit Number |
14080395 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2014-08-22 15:06:49 | ****PROVISO**** | | | ****REVISION REQUIRED**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | THE PRODUCT APPROVALS SUBMITTED WERE ALREADY SUBMITTED | | | WITH THE MASTER. THEREFORE, THE PRODUCT APPROVALS | | | SUBMITTED WITH THIS APPLICATION WILL NOT BE STAMPED. | | | | | | ENGINEERING PREPARED BY TURQUOISE ENGINEERING LLC DATED | | | 8/18/2014 REFERS TO TABLE 1D, SYSTEM E, SYSTEM W9, PG | | | 6/16. ASSEMBLY CIRCLED ON THE PRODUCT APPROVAL IS A | | | DIFFERENT ASSEMBLY, AND THE PRODUCT APPROVAL IS 24 | | | PAGES. ENHANCED FASTENING PROPOSED APPEARS COMPLIANT, | | | BUT ENGINEERING SHOULD REFER TO THE CORRECT ASSEMBLY | | | AND PAGE NUMBER. REVISE ENGINEERING AND SUBMIT AS A | | | REVISION WITH FEES. | | | | | | ALTERNATIVELY, APPLICANT CAN RESUBMIT. | | | | | | | | | |
|