| Notes |
| Date |
Text |
| 2014-08-13 15:37:58 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. ON THE METAL ROOFING PRODUCT APPROVAL, INDICATE | | | METHOD OF FASTENING PROPOSED FOR ZONES 1, 2, AND 3, FBC | | | 1609. | | | | | | 2. THE ASSEMBLY PROPOSED FOR THE FLAT DECK HAS A DESIGN | | | PRESSURE LIMITATION OF -52.5. THIS DOES NOT MEET THE | | | DESIGN PRESSURES FOR ZONES 2 & 3. SEE NOTE 8 ON PAGE 2; | | | EITHER PROVIDE ENGINEERING FOR ENHANCED FASTENING OR | | | SELECT A DIFFERENT ASSEMBLY IF ONE IS AVAILABLE WHICH | | | MEETS THE MINIMUM DESIGN PRESSURES. SEE COMMENT # 3. | | | | | | 3. PROVIDE THE BUILDING HEIGHT SO DESIGN PRESSURES CAN | | | BE DETERMINED OR CONFIRMED (IF PROVIDED BY CONTRACTOR | | | UPON RESUBMITTAL), FBC 1609. | | | | | | |
|