| Notes |
| Date |
Text |
| 2014-09-02 17:02:28 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. FBC 1609, PLEASE CLARIFY ROOF PRESSURES. WERE | | | PRESSURES CALCULATED FOR C&C OR MWFRS? THEY APPEAR LOW | | | FOR C&C. IF PLYWOOD SHEATHING IS TO BE DESIGNED WITH | | | C&C PRESSURES, WHY WOULD MWFRS PRESSURES BE USED, IF | | | THAT IS THE CASE? PLEASE EITHER REVISE PRESSURES OR | | | PROVIDE EXPLANATION. FEEL FREE TO CONTACT ME IF YOU | | | NEED MORE CLARIFICATION. | | | | | | 2. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR | | | THE ROOF PANEL AND FOR ACM FASCIA PANELS, FAC9N-3, FBC | | | 1609. | | | | | | ON THE PRODUCT APPROVAL, INDICATE METHOD OF ATTACHMENT | | | IF THERE IS MORE THAN ONE OPTION. | | | | | | 3. PROVIDE ROOF PRESSURES FOR ZONES 1, 2, AND 3. | | | PRODUCT APPROVAL TO BE CLEAR AS TO WHICH FASTENING | | | PROPOSED FOR EACH ZONE, FBC 1609. | | | | | | |
|