| 2014-08-27 10:55:20 | 14080325 |
| | 6710 S. DIXIE HWY |
| | POSH PET HOTEL |
| | |
| | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | REVIEW COMMENTS. |
| | |
| | PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN |
| | WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY |
| | CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5; |
| | 505.5.3; T. 505.5.3 |
| | |
| | CONFIRM THAT THE INTERIOR AND EXTERIOR LIGHTING |
| | CONTROLS PROVIDED FUNCTION IN ACCORDANCE WITH THE |
| | FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS SHALL |
| | BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME |
| | SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST |
| | 10 HOURS. VERIFY THE LIGHTING AND SIGN TIME CLOCKS HAVE |
| | BATTERY BACKUP. FBC ENERGY CONSERVATION 505.2 |
| | |
| | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION |
| | FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN |
| | DISCONNECTING MEANS. NEC 110.16, 110.22 |
| | |
| | PROVIDE AN ELECTRICAL RISER PLAN OF THE ELECTRICAL |
| | SERVICE WITH A SUMMERY LOAD CALCULATION. PROVIDE PANEL |
| | BOARD SCHEDULES SHOWING THE BRANCH CIRCUITS AS |
| | BALANCED. INDICATE THE FAULT CURRENT RATINGS OF THE |
| | EQUIPMENT. VERIFY THE ELECTRICAL SERVICE MAINS SERVING |
| | THIS BUILDING ARE SIX OR LESS AND GROUPED IN ONE |
| | LOCATION. VERIFY SAFE WORKING CLEARANCE HAVE BEEN |
| | PROVIDED FOR THE SERVICE, PANEL BOARDS AND DISCONNECTS. |
| | NEC 110.26, 215.5, 230.71 240.24(D) |
| | |
| | VERIFY THE ELECTRICAL DISCONNECTING MEANS AND PANEL |
| | BOARDS HAVE A FAULT CURRENT RATING THAT IS SUFFICIENT |
| | AT NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. INDICATE THE MAXIMUM AVAILABLE FAULT |
| | CURRENT AT THE SERVICE POINT FROM THE ELECTRICAL |
| | UTILITY. NEC 110.9, 110.10 |
| | |
| | PROVIDE SHOW WINDOW LIGHTING RECEPTACLES. NEC 210.62 |
| | |
| | PROVIDE A SIGN CIRCUIT AND DISCONNECT. NEC 600.5, |
| | |
| | VERIFY EXISTING HEATING AND AIR CONDITIONING EQUIPMENT |
| | HAVE A GFCI PROTECTED RECEPTACLE AVAILABLE WITHIN 25 |
| | FEET. NEC 210.63 |
| | |
| | NOTE: A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR FIRE |
| | ALARM SYSTEMS, VIDEO, SECURITY, VOICE, POS, SITE |
| | LIGHTING, SIGNS AND DATA SYSTEMS |
| | |
| | ROBERT LECKY, CBO |
| | ELECTRICAL PLANS REVIEW |
| | 561-373-3701 |
| | [email protected] |
| | |