| Notes |
| Date |
Text |
| 2014-08-15 15:10:48 | NOTES; | | | 1.MUST SUBMIT THE 'INPUT DATA REPORT " FORMS WHICH ARE | | | PART OF THE ENERGY CALCULATIONS. | | | 2.PROVIDE SIZING CALCULATIONS AS REQUIRED BY THE | | | FLORIDA ENERGY CODE SEC101.4.7.1.2. | | | 3.PAGE 7 OF 7 OF THE ENERGY CALCULATIONS MUST BE | | | COMPLETELY FILLED OUT. | | | 4.THE ENERGY AND SIZING CALCULATIONS MUST BE | | | SIGNED,SEALED AND DATED BY THE ARCHITECT/ENGINEER OF | | | RECORD. | | | 5.PROVIDE AUTOMATIC SHUTOFF DAMPER AS REQUIRED BY THE | | | ENERGY CODE SEC.503.2.4.4 AND503.2.5.4. | | | 6.SHOW ON PLAN DETAIL OF THE INSTALLATION OF THE A/C | | | UNITS INCLUDING HOW THEY ARE SECURED TO ROOF STRUCTURE | | | AND ALSO TO THE ROOF CURB. | | | REVIEWED BY JOHN ARITON. PLEASE CALL HAROLD MOSER AT | | | 561-805-6732 IF YOY HAVE ANY QUESTIONS. | | | |
|