2014-08-15 15:10:48NOTES;
 1.MUST SUBMIT THE 'INPUT DATA REPORT " FORMS WHICH ARE
 PART OF THE ENERGY CALCULATIONS.
 2.PROVIDE SIZING CALCULATIONS AS REQUIRED BY THE
 FLORIDA ENERGY CODE SEC101.4.7.1.2.
 3.PAGE 7 OF 7 OF THE ENERGY CALCULATIONS MUST BE
 COMPLETELY FILLED OUT.
 4.THE ENERGY AND SIZING CALCULATIONS MUST BE
 SIGNED,SEALED AND DATED BY THE ARCHITECT/ENGINEER OF
 RECORD.
 5.PROVIDE AUTOMATIC SHUTOFF DAMPER AS REQUIRED BY THE
 ENERGY CODE SEC.503.2.4.4 AND503.2.5.4.
 6.SHOW ON PLAN DETAIL OF THE INSTALLATION OF THE A/C
 UNITS INCLUDING HOW THEY ARE SECURED TO ROOF STRUCTURE
 AND ALSO TO THE ROOF CURB.
 REVIEWED BY JOHN ARITON. PLEASE CALL HAROLD MOSER AT
 561-805-6732 IF YOY HAVE ANY QUESTIONS.
  