| 2014-09-10 10:32:29 | PLAN REVIEW COMMENTS |
| | |
| | |
| | 1ST REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | BUILDING |
| | |
| | 1) FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. SUBMIT PRODUCT APPROVALS FOR THE SINGLE HUNG |
| | WINDOWS AND HAVE THE DESIGNER REVIEW AND APPROVE ALL OF |
| | THEM IN WRITING. |
| | |
| | 2) THE WIND-LOAD PRESSURES FOR THE WINDOWS AND EXTERIOR |
| | DOORS ARE A LITTLE LOW. THE PRESSURES FOR A 10 SQFT |
| | OPENING IN 170MPH VULT, 132 VASD EXPOSURE C WITH A 15' |
| | MEAN ROOF HEIGHT IS +37.9 PSF, -41.1 PSF IN WALL ZONE 4 |
| | AND +37.9 PSF, -50.7 PSF IN WALL ZONE 5. PLEASE REVIEW |
| | AND ADJUST. |
| | |
| | 3) FBC - R 301.2.1.2 SUBMIT TWO COPIES OF AN |
| | INSTALLATION SCHEDULE AND KEY PLAN FOR THE STORM |
| | PANELS. SPECIFY THE TYPE OF ANCHOR, ANCHOR SPACING, |
| | EDGE DISTANCE, PANEL LENGTH, SEPARATION DISTANCE FROM |
| | PANEL TO GLASS AND THE APPLICABLE SECTION NUMBER FROM |
| | THE INSTALLATION DRAWINGS. |
| | |
| | 4) THE VALUATION STATED ON THE APPLICATION OF |
| | $60,000.00 IS LOW AND HAS BEEN ADJUSTED TO $199,602.00 |
| | BASED ON THE LATEST ICC VALUATION DATA. |
| | |
| | IN ORDER TO REDUCE PLAN REVIEW TIMES, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |