2014-09-10 10:32:29PLAN REVIEW COMMENTS
  
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. SUBMIT PRODUCT APPROVALS FOR THE SINGLE HUNG
 WINDOWS AND HAVE THE DESIGNER REVIEW AND APPROVE ALL OF
 THEM IN WRITING.
  
 2) THE WIND-LOAD PRESSURES FOR THE WINDOWS AND EXTERIOR
 DOORS ARE A LITTLE LOW. THE PRESSURES FOR A 10 SQFT
 OPENING IN 170MPH VULT, 132 VASD EXPOSURE C WITH A 15'
 MEAN ROOF HEIGHT IS +37.9 PSF, -41.1 PSF IN WALL ZONE 4
 AND +37.9 PSF, -50.7 PSF IN WALL ZONE 5. PLEASE REVIEW
 AND ADJUST.
  
 3) FBC - R 301.2.1.2 SUBMIT TWO COPIES OF AN
 INSTALLATION SCHEDULE AND KEY PLAN FOR THE STORM
 PANELS. SPECIFY THE TYPE OF ANCHOR, ANCHOR SPACING,
 EDGE DISTANCE, PANEL LENGTH, SEPARATION DISTANCE FROM
 PANEL TO GLASS AND THE APPLICABLE SECTION NUMBER FROM
 THE INSTALLATION DRAWINGS.
  
 4) THE VALUATION STATED ON THE APPLICATION OF
 $60,000.00 IS LOW AND HAS BEEN ADJUSTED TO $199,602.00
 BASED ON THE LATEST ICC VALUATION DATA.
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  