| Plan Review Notes For Permit 14080269 |
| Permit Number |
14080269 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-09-11 16:17:57 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. OK | | | | | | 2. FOR BEDROOM WINDOWS WHICH ARE LESS THAN 50 5/8" IN | | | HEIGHT: | | | | | | REVISE PLAN TO STATE WHAT TYPE OF WINDOW IS THERE NOW | | | IN THE BEDROOMS - AWNING, CASEMENT, SINGLE HUNG? | | | | | | REVISE PLAN TO STATE WHAT THE EXISTING CLEAR OPENING | | | DIMENSIONS ARE. CLEAR OPENING IS THE OPENING WHICH | | | EXISTS WHEN THE WINDOW IS FULLY OPEN. | | | | | | REVISE PLAN TO STATE WHAT THE PROPOSED CLEAR OPENING | | | DIMENSIONS ARE. THIS CAN BE OBTAINED FROM THE | | | MANUFACTURER | | | | | | 2ND REVIEW, EMERGENCY ESCAPE AND RESCUE OPENINGS ARE TO | | | OPERATE WITHOUT SPECIAL KNOWLEDGE OR TOOLS. INFORMATION | | | ABOUT DOUBLE HUNG WINDOWS' OPERATION HAS NOT BEEN | | | PROVIDED. PLEASE EITHER SUBMIT INFORMATION FOR | | | CONSIDERATION OR PROVIDE THE INFORMATION REQUESTED. ONE | | | OF THE BEDROOM WINDOWS IS 38" HIGH. | | | | | | 3. THE QUALIFIER'S SIGNATURE ON THE APPLICATION IS TO | | | BE NOTARIZED, FBC 107. THE OWNER'S NOTARIZED SIGNATURE | | | IS ALSO REQUIRED. | | | | | | THIS MAY BE PROVIDED AT TIME OF PERMIT PICKUP. THERE IS | | | A HOLD ON THE PERMIT; THIS CANNOT BE PICKED UP WITHOUT | | | THE APPLICATION NOTARIZED BY THE CONTRACTOR AND BY THE | | | OWNER. TWO SEPARATE APPLICATIONS (ONE WITH CONTRACTOR'S | | | SIGNATURE, ONE WITH OWNER'S SIGNATURE) CAN BE PROVIDED. | | | | | | | | | | | | | | | | | | | | | |
|