Plan Review Notes
Plan Review Notes For Permit 14080268
Permit Number 14080268
Review Stop P
Sequence Number 2
Notes
Date Text
2014-09-19 15:09:351) ALL THE COMMENTS FROM THE PREVIOUS REVIEW HAVE NOT
 BEEN ADDRESSED.
 2) 2ND REQUEST - SHOW THE LENGTH AND WIDTH OF THE
 URINAL AND TOILET STALLS ON THE FLOOR PLAN. COMPLY WITH
 THE 2010 FLORIDA PLUMBING CODE SEC.405.3.1.AND THE FAC
 SEC.604.8.2.1. SEE SHEETS A101,102, 150, 151.
 3) 2ND REQUEST - TOILET COMPARTMENT DOORS SHALL NOT
 SWING INTO THE REQUIRED COMPARTMENT AREA PER THE 2010
 FAC SEC.603.2.3, 604.8.2.2.
 4) 2ND REQUEST - DOORS SHALL NOT SWING INTO THE URINAL
 COMPARTMENTS PER THE 2010 FAC SEC. 604.8.2.2. SHT A201
 - DETAILS #1, #3, AND #7 SHOW VERTICAL GRAB BARS. GRAB
 BARS ARE NOT PERMITTED TO BE INSTALLED IN A VERTICAL
 POSITION PER THE 2010 FAC SEC. 609.4.
 5) THE REVISED PLUMBING SHEETS P-202 & P-401 SHALL BE
 INSERTED INTO THE PLANS AND THE OLD SHEETS REMOVED.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  