| Plan Review Notes For Permit 14080268 |
| Permit Number |
14080268 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-09-19 15:09:35 | 1) ALL THE COMMENTS FROM THE PREVIOUS REVIEW HAVE NOT | | | BEEN ADDRESSED. | | | 2) 2ND REQUEST - SHOW THE LENGTH AND WIDTH OF THE | | | URINAL AND TOILET STALLS ON THE FLOOR PLAN. COMPLY WITH | | | THE 2010 FLORIDA PLUMBING CODE SEC.405.3.1.AND THE FAC | | | SEC.604.8.2.1. SEE SHEETS A101,102, 150, 151. | | | 3) 2ND REQUEST - TOILET COMPARTMENT DOORS SHALL NOT | | | SWING INTO THE REQUIRED COMPARTMENT AREA PER THE 2010 | | | FAC SEC.603.2.3, 604.8.2.2. | | | 4) 2ND REQUEST - DOORS SHALL NOT SWING INTO THE URINAL | | | COMPARTMENTS PER THE 2010 FAC SEC. 604.8.2.2. SHT A201 | | | - DETAILS #1, #3, AND #7 SHOW VERTICAL GRAB BARS. GRAB | | | BARS ARE NOT PERMITTED TO BE INSTALLED IN A VERTICAL | | | POSITION PER THE 2010 FAC SEC. 609.4. | | | 5) THE REVISED PLUMBING SHEETS P-202 & P-401 SHALL BE | | | INSERTED INTO THE PLANS AND THE OLD SHEETS REMOVED. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|