| 2014-09-07 07:39:13 | WPB ADMIN. AMEND. TO 2010 FBC SEC.107.2.1. |
| | 1) SHOW THE LENGTH AND WIDTH OF THE URINAL AND TOILET |
| | STALLS ON THE FLOOR PLAN. COMPLY W/ 2010 FLORIDA |
| | PLUMBING CODE SEC.405.3.1 & FAC SEC.604.8.2.1. SHTS. |
| | A101,102,150,151. |
| | 2)THE DOOR CANNOT SWING IN TO THE CLEAR FLOOR SPACE |
| | REQUIRED FOR THE TOILET COMPARTMENTS PER THE 2010 FL. |
| | ACCESSIBILITY CODE SEC.603.2.3, 604.8.2.2. |
| | 3) DOORS SHALL NOT NOT SWING INTO THE URINAL |
| | COMPARTMENTS PER THE FL. ACCESSIBILITY CODE SEC. |
| | 604.8.2.2. |
| | SHT. A201 - DETAILS #1, #3, & #7 SHOW VERTICAL GRAB |
| | BARS. GRAB BARS INSTALLED IN A VERTICAL POSITION ARE |
| | NOT PERMITTED PER THE 2010 FAC SEC.609.4. |
| | 4) SHT. P401 - SUBMIT A LEGEND FOR THE CIRCLED NUMBERS |
| | SHOWN ON THE PLANS ( E.G. #1,11,12,14). |
| | 5)SUBMIT MANUFACTURERE'S SPECIFICATION SHEETS FOR THE |
| | SCHIER GREASE TRAP. |
| | 5) SUBMIT SIZING CALCULATIONS FOR THE GREASE TRAP AS TO |
| | THE AMOUNT GREASE THAT WILL BE GENERATED TO SPECIFY THE |
| | SIZE OF THIS TRAP. |
| | 6) SHT. P-401 - A URINAL CANNOT BE INSTALLED ON A |
| | HORIZONTAL WET VENT PER THE 2010 FPC SEC.909.1 |
| | 7) SHT. P-401- THE LAVATORIES ON THE SANITARY RISER ARE |
| | SHOWN AS BEING S-TRAPPED.S-TRAPS ARE NOT PERMITTED PER |
| | THE 2010 FPC SEC.1002.3 |
| | 8) SHT.P-401- NOT MORE THAN ONE WET-VENTED FIXTURE |
| | DRAIN SHALL DISCHARGE UPSTREAM OF THE DRY-VENTED |
| | FIXTURE DRAIN CONNECTION.FPC SEC.909.2.1. |
| | |
| | PLUMBING PLAN REVIEW |
| | TIM LARGE- |
| | CHIEF PLUMBING INSPECTOR |
| | TEL:561-805-6692 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |