Plan Review Notes
Plan Review Notes For Permit 14080268
Permit Number 14080268
Review Stop B
Sequence Number 1
Notes
Date Text
2014-08-20 11:59:31BUILDING PLAN REVIEW
 PERMIT: 14080268
 ADD: 1301 BELVEDERE RD
 CONT: WESTLAKE LLC
 TEL: (267)251-8336
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. AUG. 20/2014
 ACTION: BUILDING PROVISO
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1A) SHEET G001 OCCUPANCY TYPE SHOULD BE NOT A R2 BUT A
 R1 HOTEL 2010 FBC-B 310.1.
  
 1B) SHEET G001 EXISTING BUILDING CODE LEVEL 1, PLEASE
 SEE 2010 EXISTING BUILDING CODE LEVEL II 404.1 SCOPE.
 LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF
 SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR
 WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM,
 OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT.
  
 LEVEL II. 701.3 COMPLIANCE. ALL NEW CONSTRUCTION
 ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY
 WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE,
 BUILDING.
  
 2) SHEET A100 NOTE # 4 REMOVE DOORS IN ENTIRETY INSTALL
 ALUMINUM STOREFRONT AND GLAZING TO MATCH. SHEET A101
 INDICATES NEW STUCCO / METAL STUD INFILL WALLS WITH
 HORIZONTAL SLIDING DOORS.
  
 2A) PLEASE PROVIDE THE WIND DESIGN FOR THIS OPENING,
 NEGATIVE PRESSURES ARE TAKEN FROM THE ROOF. 2010 FBC-B
 1609.1.1 DETERMINATION OF WIND DESIGN- CHAPTER 6 OF
 ASCE 7-10. 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
 2A)(1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 2A)(2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE
 7-10.
  
 2A)(3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 2A)(4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 2A)(5) COMPONENTS & CLADDING PRESSURES POSITVE &
 NEGATIVE TABLE 1609.2(2) .
  
  
 2B) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) , EFIS SYSTEMS,
  
 2C) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2D) THE INFILL EXTERIOR WALLS WILL NEED TO SHOW HOW
 THEY WILL BE ABLE TO RESIST WIND AND PART OF THE MAIN
 WIND FORCE RESISTING SYSTEM. 2010 FBC-B 1609.1.1.
  
 2D) THE PLANS DEPICT THE USE OF WHAT APPEARS TO BE
 HORIZONTAL SLIDING DOORS WILL NEED TO MEET THE
 REQUIREMENTS OF:
  
 1008.1.4.3 HORIZONTAL SLIDING DOORS.
 IN OTHER THAN GROUP H OCCUPANCIES, HORIZONTAL SLIDING
 DOORS PERMITTED TO BE A COMPONENT OF A MEANS OF EGRESS
 IN ACCORDANCE WITH EXCEPTION 6 TO SECTION 1008.1.2
 SHALL COMPLY WITH ALL OF THE FOLLOWING CRITERIA:
  
 1. THE DOORS SHALL BE POWER OPERATED AND SHALL BE
 CAPABLE OF BEING OPERATED MANUALLY IN THE EVENT OF
 POWER FAILURE.
  
 2. THE DOORS SHALL BE OPENABLE BY A SIMPLE METHOD FROM
 BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR EFFORT.
  
 3. THE FORCE REQUIRED TO OPERATE THE DOOR SHALL NOT
 EXCEED 30 POUNDS (133 N) TO SET THE DOOR IN MOTION AND
 15 POUNDS (67 N) TO CLOSE THE DOOR OR OPEN
 IT TO THE MINIMUM REQUIRED WIDTH.
  
 4. THE DOOR SHALL BE OPENABLE WITH A FORCE NOT TO
 EXCEED 15 POUNDS (67 N) WHEN A FORCE OF 250 POUNDS
 (1100 N) IS APPLIED PERPENDICULAR TO THE DOOR
 ADJACENT TO THE OPERATING DEVICE.
  
 5. THE DOOR ASSEMBLY SHALL COMPLY WITH THE APPLICABLE
 FIRE PROTECTION RATING AND, WHERE RATED, SHALL BE
 SELF-CLOSING OR AUTOMATIC CLOSING BY SMOKE
 DETECTION IN ACCORDANCE WITH SECTION 715.4.8.3, SHALL
 BE INSTALLED IN ACCORDANCE WITH NFPA 80 AND SHALL
 COMPLY WITH SECTION 715.
  
 6. THE DOOR ASSEMBLY SHALL HAVE AN INTEGRATED STANDBY
 POWER SUPPLY.
  
 7. THE DOOR ASSEMBLY POWER SUPPLY SHALL BE ELECTRICALLY
 SUPERVISED.
  
 8. THE DOOR SHALL OPEN TO THE MINIMUM REQUIRED WIDTH
 WITHIN 10 SECONDS AFTER ACTIVATION OF THE OPERATING
 DEVICE.
  
 9. IN APARTMENT BUILDINGS, HOTELS AND DORMITORIES,
 HORIZONTAL SLIDING DOORS SHALL NOT BE USED ACROSS
 CORRIDORS.
  
 1008.1.10 PANIC AND FIRE EXIT HARDWARE.
 DOORS SERVING A GROUP H OCCUPANCY AND DOORS SERVING
 ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE IN
 A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED WITH A
 LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
 EXCEPTIONS: 1. A MAIN EXIT OF A GROUP A OCCUPANCY IN
 COMPLIANCE WITH SECTION 1008.1.9.3, ITEM 2.
  
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  