| 2015-01-14 11:23:45 | DATE: 01/14/2015 |
| | PROJECT: 36TH ST REAR BLDG |
| | PERMIT#: 14080234 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC, WPB AMENDMENTS TO THE FBC, |
| | CHAPTER 1, ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 4TH ELECTRICAL PLAN REVIEW |
| | ACTION: APPROVED WITH EXCEPTION |
| | |
| | PROVIDE AN AS BUILT FOR ELECTRICAL INSPECTOR ON SITE |
| | PER EXISTING CONDITIONS. |
| | |
| | 1) FBC-WPB AMENDMENTS 107.3.5 |
| | INDICATE THE TRUE SCOPE AND EXTENT OF ELECTRICAL |
| | IMPROVEMENTS. THE APPLICATION STATES "INTERIOR |
| | IMPROVEMENTS AND WINDOW REPLACEMENT" THE PLAN PROVIDES |
| | ELECTRICAL DETAILS AND NOTES. CLARIFICATION IS |
| | REQUIRED. INDICATE WHAT IS EXISTING TO REMAIN. WHAT IS |
| | REMOVED AND OR RELOCATED AND WHAT IS COMPLETELY NEW OR |
| | SIMPLY REPLACED. |
| | |
| | 2) PROVIDE A RISER DIAGRAM, LOAD CALCULATION AND A |
| | PANEL SCHEDULE. NEC 215.5, 220, 408.4 |
| | |
| | 3) IDENTIFY THE LOCATION AND SIZE OF THE ELECTRICAL |
| | SERVICE, MAIN DISCONNECT, PANEL, CONDUITS AND FEEDER |
| | CONDUCTORS. |
| | |
| | 4) IDENTIFY THE CIRCUITRY FOR THE OUTLETS AND LIGHTS |
| | THROUGHOUT TO COINCIDE WITH THE PANEL CIRCUIT |
| | DIRECTORY. FBC, WPB AMENDMENTS 107.3.2 |
| | |
| | 5) VERIFY RECEPTACLES SHALL BE INSTALLED SUCH THAT NO |
| | POINT MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY |
| | WALL SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE |
| | OUTLET OR 24" FOR KITCHEN COUNTERTOPS. 210.52(A)(1), |
| | 210.52(C)(1), |
| | |
| | 6) ALL HABITABLE LIVING AREA REQUIRES A SWITCHED LIGHT |
| | OR SWITCH CONTROLLED OUTLET. NEC 210.70. THE LIVING |
| | ROOM HAS NO SWITCH CONTROLLED LIGHT OUTLET. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |