| 2014-12-16 10:58:36 | 12/16/2014 |
| | PROJECT: 438 36TH ST, REAR |
| | PERMIT#: 14080234 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 3RD ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE A RISER DIAGRAM, AND A PANEL SCHEDULE. EVERY |
| | CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY |
| | IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC |
| | PURPOSE OR USE. NEC 408.4, NEC 215.5, FBC-WPB |
| | AMENDMENTS 107.3.5 |
| | |
| | 2) IDENTIFY THE LOCATIONS OF THE ELECTRICAL SERVICE AND |
| | IDENTIFY THE CIRCUITRY OF THE OUTLETS AND LIGHTS |
| | THROUGHOUT TO COINCIDE WITH THE PANEL CIRCUIT |
| | DIRECTORY. |
| | |
| | 3) REVISE LOAD CALCULATION IN COMPLIANCE WITH THE NEC. |
| | ALL SQUARE FOOTAGE HAS NOT BEEN ACCOUNTED FOR IN THE |
| | CALCULATION PROVIDED. LOADS FOR NEW CIRCUITS OR |
| | EXTENDED CIRCUITS IN PREVIOUSLY WIRED DWELLING UNITS |
| | SHALL BE CALCULATED IN ACCORDANCE WITH EITHER 220.12 OR |
| | 220.14, AS APPLICABLE. NEC 220.16(2) |
| | |
| | 4) VERIFY RECEPTACLES SHALL BE INSTALLED SUCH THAT NO |
| | POINT MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY |
| | WALL SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE |
| | OUTLET OR 24" FOR KTCHEN COUNTERTOPS. 210.52 (A)(1), |
| | 210.52(C)(1), |
| | |
| | 5) ALL HABITABLE LIVING AREA REQUIRES A SWITCHED LIGHT |
| | OR SWITCH CONTROLLED OUTLET. NEC 210.70 |
| | |
| | 6) OCCUPIABLE BALCONIES AND PORCHES OVER 20 SQ FT MUST |
| | HAVE A GFI RECEPTACLE OUTLET. NEC 210.52(E)(3) |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| 2014-10-31 16:07:58 | |
| | |