Plan Review Notes
Plan Review Notes For Permit 14080215
Permit Number 14080215
Review Stop E
Sequence Number 1
Notes
Date Text
2014-08-07 08:42:19DATE: 8/6/2014
 PROJECT: FACADE RENNOVATION 409 24TH ST
 PERMIT#: MASTER:13110608 ELECTRIC SUB: 14011697
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) PROVIDE ELECTRICAL PLANS TO INDICATE THE FOLLOWING:
 FBC 107.2.1
 LOCATION OF THE EXISTING JUNCTION BOX WITH 110V
 CIRCUIT.
 LOCATION OF THE TRANSFORMER.
 LOCATION OF THE TIMER.
 LOCATION AND NUMBER OF REMOTE LED DRIVER(S).
 LOCATION OF LED LIGHTING.
 WIRING AND TERMINATION DETAIL INDICATING THE METHODS
 AND MATERIALS USED FROM THE SOURCE JUNCTION BOX TO THE
 LED LIGHTING.
 THE TOTAL LENGTH AND CONNECTED LOAD OF LED LIGHTING.
 NAME AND SIGNATURE OF THE DESIGN PROFESSIONAL
  
  
 2) PROVIDE ITEM NUMBERS AND MAUFACTURER LISTING FROM
 APPROVED TESTING LABRATORY ON THE FOLLOWING: NEC110.3
 LED DRIVER.
 LED LIGHTING
 TRANSFORMER
 TIMER
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT
 /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM
 ITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  