2014-09-02 14:26:08FAILED
  
 1) THE MANAGEMENT STAMP WAS NOT PROVIDED ON THE
 DRAWINGS.
  
 2) NO BUILDING ELEVATION PLAN WAS PROVIDED TO SHOW
 WHERE THE AWNINGS ARE LOCATED. ALL THE PROPOSED AWNING
 TYPES SHALL BE SPECIFICALLY TIED TO THEIR LOCATION ON
 THE ELEVATION PLAN.
  
 3) THE ELEVATION PLAN SHALL VERIFY THAT THE MINIMUM
 CLEARANCE OF EACH AWNING IS EIGHT (8) FEET ABOVE GRADE.
  
 4) THE AWNINGS SHALL BE CENTERED ABOVE THE OPENINGS
 THAT THEY COVER.
  
 5) PLEASE VERIFY THE NUMBER OF SUPPLIED FABRIC AWNINGS.
 THE PLANS SEEM TO CALL OUT MORE AWNINGS THAN ARE
 ACTUALLY SHOWN ON THE LATEST APPROVED ELEVATION
 DRAWINGS.
  
 6) THE LOGOS ON THE VALANCE OF THE ULTA AWNING REQUIRE
 SEPARATE PERMITTING AS PART OF THE ALLOWED WALL SIGNAGE
 AND MAY NOT BE INSTALLED AS PART OF THIS PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.