| 2014-09-02 10:38:48 | FAILED | | | | | | 1) THE MANAGEMENT STAMP WAS NOT PROVIDED ON THE | | | DRAWINGS. | | | | | | 2) NO BUILDING ELEVATION PLAN WAS PROVIDED TO SHOW | | | WHERE THE AWNINGS ARE LOCATED. THE FOUR PROPOSED AWNING | | | TYPES SHALL BE SPECIFICALLY TIED TO THEIR LOCATION ON | | | THE ELEVATION PLAN. | | | | | | 3) THE ELEVATION PLAN SHALL VERIFY THAT THE MINIMUM | | | CLEARANCE OF EACH AWNING IS EIGHT (8) FEET ABOVE GRADE. | | | | | | 4) THE AWNINGS SHALL BE CENTERED ABOVE THE OPENINGS | | | THAT THEY COVER. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | 2014-08-06 14:45:06 | 8/6/14 ZONING SENT TO AV. SG |
|