| Plan Review Notes For Permit 14080179 |
| Permit Number |
14080179 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-08-20 10:33:22 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE ENGINEERING FOR THE GENERATOR PAD DOES NOT HAVE | | | THE ENGINEER'S SEAL OR HAND SIGNED SIGNATURE AS | | | REQUIRED BY FAC 61G-23.002. | | | | | | 2) THE MODEL NUMBER OF THE GENERAC GENERATOR IN THE | | | SPECIFICATIONS THAT WERE SUBMITTED IS NOT LISTED IN THE | | | SCHEDULE FOR APPROVED MODELS ON SHEET 1 OF THE | | | PREFABRICATED PAD ENGINEERING. FBCR 301.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|