| Plan Review Notes For Permit 14080175 |
| Permit Number |
14080175 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-08-15 10:10:59 | NOTES; | | | 1.PROVIDE OUTSIDE AIR CALCULATIONS BASED ON THE TOTAL | | | OCCUPANT LOAD AND AS REQUIRED BY 2010 FMC, TABLE 403.3 | | | OR ASHRAE 62.1-2004.USE EQUATION 4-1 AS REQUIRED BY SEC | | | 403.3.1.1. | | | 2.SHOW ON PLANS LOCATION OF ALL FIRE DAMPERS IF ANY. | | | 3.CLARIFY ON PLANS IF YOU HAVE TRANSFER DUCTS( JUMPER) | | | OR TRANSFER R/A GRILLS AS SHOWN ON PLANS. | | | 4.INDICATE ON PLANS THE SIZES OF ALL RETURN AIR | | | TRANSFER DUCTS AND SUPPLY AIR DUCTS. | | | 5.IF DUCTS PENETRATE THROUGH FIRE/SMOKE RATED | | | PARTITIONS THEY SHALL BE PROTECTED WITH APPROVED | | | FIRE/SMOKE DAMPERS,INSTALLED IN ACCORDANCE WITH THEIR | | | LISTING AS REQUIRED BY FBC-MECHANICAL SEC.607.1.1. | | | 6.SINCE THE BUILDING HAS EXISTING SMOKE EVAC.SYSTEM, | | | THEN PROVIDE SUFFICIENT INFORMATION ON PLANS AND | | | INDICATE IF THE SYSTEM HAS BEEN AFFECTED BY THIS | | | ALTERATION. ALSO INCLUDE OPERATIONAL AND ACCEPTANCE | | | TESTING PROCEDURES AS REQUIRED BY FMC,SEC.513.1 AND | | | 513.2. | | | 7.INDICATE ON PLANS COMPLIANCE TO FMC, SEC.602.2.1 FOR | | | MATERIALS WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR | | | SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND | | | A SMOKE DEVELOPED INDEX NOT MORE THAN 50 WHEN TESTED IN | | | ACCORDANCE WITH ASTM E 84 OR UL 723. | | | REVIEWED BY JOHN ARITON.FOR QUESTION PLEASE CALL HAROLD | | | MOSER AT 561-805-6732. |
|