2014-09-08 16:05:48DATE: 9/8/2014
 PROJECT: LUX AUTO SPA
 PERMIT#: 14080148
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW FOR FOUNDATION PERMIT ONLY
 ACTION: DENIED
  
 1) PG. E-3. THERE ARE A COUPLE OF SYMBOLS AND A NOTE
 THAT REFFERENCE GOUNDING BUT NO DETAILS THAT REFFERENCE
 THE FOUNDATION STEEL REQUIRED BY NEC 250.52(3)
 CONCRETE-ENCASED ELECTRODE.
 PROVIDE A COMPLETE GROUNDING ELECTRODE SYSTEM PER NEC
 250 PART III. GROUNDING ELECTRODE SYSTEM INCLUDING THE
 CONCRETE ENCASED ELECTRODE PER NEC 250.52.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO
 SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED
 SHEETS FOR COMPARATIVE REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  