| Plan Review Notes For Permit 14080148 |
| Permit Number |
14080148 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-08 16:05:48 | DATE: 9/8/2014 | | | PROJECT: LUX AUTO SPA | | | PERMIT#: 14080148 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW FOR FOUNDATION PERMIT ONLY | | | ACTION: DENIED | | | | | | 1) PG. E-3. THERE ARE A COUPLE OF SYMBOLS AND A NOTE | | | THAT REFFERENCE GOUNDING BUT NO DETAILS THAT REFFERENCE | | | THE FOUNDATION STEEL REQUIRED BY NEC 250.52(3) | | | CONCRETE-ENCASED ELECTRODE. | | | PROVIDE A COMPLETE GROUNDING ELECTRODE SYSTEM PER NEC | | | 250 PART III. GROUNDING ELECTRODE SYSTEM INCLUDING THE | | | CONCRETE ENCASED ELECTRODE PER NEC 250.52. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. SEE LINK: | | | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ | | | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF | | | | | | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO | | | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED | | | SHEETS FOR COMPARATIVE REVIEW. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|