2014-09-12 11:30:351) SHOW THE CLEAR FLOOR SPACE FOR THE URINAL ON SHT.
 A7.2. COMPLY W/ FL. ACCESS. CODE.SEC.305.
 2) THE PLANS SHOW THE DOORS ON THE TOILET COMPARTMENTS
 SWINGING INTO THE COMPARTMENT. THE DOORS CANNOT SWING
 INTO THE COMPARTMENT PER THE FAC SEC.604.8.1.2. REVISE
 ALL SHEETS.
 3) SHT. A7.2-TYPICAL TOILET ROOM DIMENSIONS SHOWS GRAB
 BARS INSTALLED IN A VERTICAL POSITION.GRAB BARS SHALL
 BE INSTALLED HORIZONTALLY PER THE FAC SEC. 609.4.
 4) SHT. P1.1 - BEVERAGE DISPENSERS SHALL BE EQUIPPED W/
 BACKFLOW PREVENTERS PER THE 2010 FPC SEC.608.16.1.
 5)THE FLOOR PLAN SHOWS FIXTURES BEING REMOVED AND
 RELOCATED IN THE RESTROOMS; SUBMIT A WATER RISER AND
 SANITARY RISER FOR ALL THE CHANGES BEING MADE TO THE
 PLUMBING SYSTEM.
 60 SUBMIT A LEGEND FOR THE CIRCLED NUMBERS AT THE
 PLUMBING FIXTURES SHOWN IN THE RESTROOMS.WPB ADMIN.
 AMEND. TO 2010 FBC SEC. 107.2.1.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR