| Plan Review Notes For Permit 14080118 |
| Permit Number |
14080118 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-12 11:30:35 | 1) SHOW THE CLEAR FLOOR SPACE FOR THE URINAL ON SHT. | | | A7.2. COMPLY W/ FL. ACCESS. CODE.SEC.305. | | | 2) THE PLANS SHOW THE DOORS ON THE TOILET COMPARTMENTS | | | SWINGING INTO THE COMPARTMENT. THE DOORS CANNOT SWING | | | INTO THE COMPARTMENT PER THE FAC SEC.604.8.1.2. REVISE | | | ALL SHEETS. | | | 3) SHT. A7.2-TYPICAL TOILET ROOM DIMENSIONS SHOWS GRAB | | | BARS INSTALLED IN A VERTICAL POSITION.GRAB BARS SHALL | | | BE INSTALLED HORIZONTALLY PER THE FAC SEC. 609.4. | | | 4) SHT. P1.1 - BEVERAGE DISPENSERS SHALL BE EQUIPPED W/ | | | BACKFLOW PREVENTERS PER THE 2010 FPC SEC.608.16.1. | | | 5)THE FLOOR PLAN SHOWS FIXTURES BEING REMOVED AND | | | RELOCATED IN THE RESTROOMS; SUBMIT A WATER RISER AND | | | SANITARY RISER FOR ALL THE CHANGES BEING MADE TO THE | | | PLUMBING SYSTEM. | | | 60 SUBMIT A LEGEND FOR THE CIRCLED NUMBERS AT THE | | | PLUMBING FIXTURES SHOWN IN THE RESTROOMS.WPB ADMIN. | | | AMEND. TO 2010 FBC SEC. 107.2.1. | | | | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|