Plan Review Notes
Plan Review Notes For Permit 14080118
Permit Number 14080118
Review Stop E
Sequence Number 1
Notes
Date Text
2014-08-07 14:50:01PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN
 SHOWING COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5;
 505.5.3; T. 505.5.3
  
 PROVIDE OR CONFIRM THAT THE INTERIOR AND EXTERIOR
 LIGHTING CONTROLS PROVIDED FUNCTION IN ACCORDANCE WITH
 THE FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS
 SHALL BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME
 SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST
 10 HOURS. FBC ENERGY CONSERVATION 505.2
  
 PROVIDE LIGHTING CONTROLS ON THE SIGN CIRCUIT.
 AUTOMATIC CONTROLS SHALL BE CAPABLE OF RETAINING
 PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER
 FOR A PERIOD OF AT LEAST 10 HOURS. FBC ENERGY
 CONSERVATION 505.2
  
 ROBERT LECKY
 ELECTRICAL PLANS REVIEW