| 2014-08-26 08:33:38 | BUILDING PLAN REVIEW |
| | PERMIT: 14080118 |
| | ADD: 1531 BELVEDERE RD. |
| | CONT: CORPORATE PROPERTY SERVICES, INC |
| | TEL: (954) 426-5144 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. AUG.26/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) THE SUBMITTED PRODUCT APPROVALS HAVE NOT BEEN |
| | REVIEWED BY THE DESIGNER OF RECORD. 2010 FBC 107.3.4.1 |
| | PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED |
| | BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 2) SUBMITTED NOA 12-0201.07 SMI-090 ALUMINUM WINDOW |
| | WALL SYSTEM MISSING THE NOA FOR THE NEW GLAZED DOOR ON |
| | THE DRIVE THRU ELEVATION. 2010 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE |
| | 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR |
| | CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | |
| | 3) THE ROOFING APPROVAL FL 16039-R3 WAS SUBMITTED, NO |
| | SUB-SYSTEM NOR PRESSURES WERE IDENTIFIED. 2010 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1, 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY |
| | THE CODE, THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, |
| | DESCRIBE AND DELINEATE THE TYPE OF ROOFING SYSTEM, |
| | MATERIALS, FASTENING REQUIREMENTS, FLASHING |
| | REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE |
| | REQUIRED TO BE |
| | INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL |
| | INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR |
| | THE SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR |
| | ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH |
| | THE CONSTRUCTION DOCUMENTS |
| | |
| | 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | JAMES A. WITMER CBO |