| Plan Review Notes For Permit 14080085 |
| Permit Number |
14080085 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-10-02 18:25:53 | RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- A/C PLAN SUBMITTED IN DRAWING M-1 DOESN'T MATCH | | | ARCHITECTURAL PLAN. A/C PLAN SHOWS 14 X 8 PASS-THROUGH | | | RETURN, WHILE ARCHITECTURAL PLAN ON SHEET A-1 SHOWS | | | R.A.G. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 CITY | | | AMENDMENTS TO FBC. | | | | | | 2- PERSON RESPONSIBLE FOR THE A/C DESIGN TO PROVIDE | | | NAME AND SIGNATURE AS REQUIRED BY SEC. 107.2.1 CITY | | | AMENDMENTS TO FBC. | | | | | | ***NOTE: SEPARATE MECHANICAL PERMIT WILL BE REQUIRED | | | AND VALUATION FOR THE MECHANICAL WORK IS NOT INCLUDED | | | IN THE MASTER PERMIT APPLICATION | | | | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|