2015-01-08 10:51:501) SHOW THE REQUIRED KNEE AND TOE CLEARANCES UNDER THE
 LAVATORY. COMPLY WITH THE 2010 FBC, ACCESSIBILITY
 SECS.306 & 606.
 2) THE HEIGHT OF THE GRAB BARS SHALL BE MEASURED FROM
 THE FINISH FLOOR TO THE TOP OF THE GRIPPING SURFACE,
 NOT TO THE CENTERLINE OF THE GRAB BAR AS SHOWN. FL.
 ACCESSIBILITY CODE SEC. 609.4.
 3) SUBMIT A WATER RISER DIAGRAM FOR REVIEW PER THE WPB
 AMEND TO 2010 FBC SEC. 107.3.5.1.3.
 4) A CLEANOUT IS REQUIRED IN THE BASE OF THE WASTE
 STACK PER THE 2010 FPC SEC.708.3.4.
 5) INDICATE IF THE DOOR TO THE RESROOM IS EQUIPPED WITH
 A CLOSER AND LATCH. IF SO THEN A MIN. OF 12 INCHES OF
 CLEARANCE SHALL BE PROVIDED PARALLEL TO THE DOORWAY
 BEYOND THE LATCH SIDE PER THE FAC TABLE 404.2.4.1.SHOW
 THE DIMENSION ON THE PLAN.
 6) COMPLY WITH THE BUILDING PLAN REVIEW COMMENTS FOR
 THE WALLS.
  