| 2014-08-22 17:30:49 | ****PROVISO**** |
| | ****ISSUED AT CONTRACTOR'S RISK**** |
| | ****REVISION REQUIRED PRIOR TO FIRST INSPECTION**** |
| | ****REVISED ON 8/26/14**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC 109, VALUE TO INCLUDE THE VALUE OF LABOR, |
| | MATERIALS, OVERHEAD, PROFIT, ENGINEERING/ARCHITECTURE. |
| | VALUE OF $850 ON PERMIT APPLICATION IS TOO LOW. PROVIDE |
| | A COPY OF THE CONTRACT FOR THIS JOB. VALUE TO BE |
| | REASONABLE, OTHERWISE AN ESTIMATE USING MARSHALL & |
| | SWIFT WILL BE REQUIRED. |
| | |
| | ARCHITECT TO REVISE PLAN TO INCLUDE WIND DESIGN |
| | CRITERIA, FBC1603.1.4. |
| | |
| | ARCHITECT TO REVISE PLAN TO INCLUDE FLOOD DESIGN DATA, |
| | FBC 1603.1.7. AN ELEVATION CERTIFICATE WILL BE HELPFUL |
| | IN DETERMINING DESIGN CRITERIA REQUIRED. THE ELEVATION |
| | CERTIFICATE MAY BE SENT VIA EMAIL. |
| | |
| | DECK ELEVATIONS (DRAWINGS) MAY BE REQUIRED DEPENDING ON |
| | INFORMATION ON THE ELEVATION CERTIFICATE. IT IS NOT |
| | CLEAR HOW HIGH THE DECK IS, AND WHETHER THERE IS AN |
| | ENCLOSURE UNDER THE DECK OR OPEN SPACE. COMPLIANCE WITH |
| | NFIP REGULATIONS (FLOOD/FEMA) AND FBC 1603.1.7 CANNOT |
| | BE DETERMINED AT THIS TIME. |
| | |
| | A MORE COMPLETE PLAN REVIEW WILL BE PROVIDED AFTER |
| | RECEIPT OF AN ELEVATION CERTIFICATE. |
| | |
| | ****NEW COMMENT 8/26/2014**** |
| | |
| | ADD FLOOR LOAD DESIGN CRITERIA TO THE PLAN (DEAD LOAD |
| | AND LIVE LOAD), SEE FBC TABLE 1607.1, FBC 1603.1. |
| | |