| Plan Review Notes For Permit 14080071 |
| Permit Number |
14080071 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2014-09-18 12:00:17 | BUILDING APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES | | | IN THIS PLAN PRIOR TO INSPECTION WILL RESULT IN FAILED | | | INSPECTION(S) AND THE ASSESSMENT OF | | | RE-INSPECTION FEE(S). REVISIONS REQUIRE ADDITIONAL | | | REVIEWS WITH ASSOCIATED FEES. | | | | | | SHEET M2.0 REVISION # 1 SEE CU-1 IS LOCATED WITHIN A | | | PLENUM. PROVIDE COMPLIANCE WITH: | | | 2010 FBC-MECHANICAL 602.2.1 MATERIALS WITHIN PLENUMS. | | | EXCEPT AS REQUIRED BY SECTIONS | | | 602.2.1.1 THROUGH 602.2.1.6, MATERIALS WITHIN PLENUMS | | | SHALL BE NONCOMBUSTIBLE OR SHALL | | | HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A | | | SMOKE-DEVELOPED INDEX OF NOT MORE | | | THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL | | | 723. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|