| Plan Review Notes For Permit 14080071 |
| Permit Number |
14080071 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-08-18 14:28:19 | 8/18/14 | | | NOTES: | | | 1.SHOW ON PLANS THE LOCATION OF THE CONDENSING UNIT FOR | | | DS-1 SYSTEM. | | | 2.CLARIFY IF THE CFM'S FOR THE SYSTEM IS 1070 OR 325 | | | CFM'S AS SHOWN ON PLANS. | | | 3.PROVIDE EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY | | | THE FEC SEC.101.4.7.2. | | | 4.SHOW DISCHARGE LOCATION OF THE CONDENSATE DRAINAS | | | REQUIRED BY FMC,SEC305 AND SEC.1503.7 OF THE FBC. | | | 5.COMPLY WIT FMC SEC.307.2.3 WHICH REQUIRES UNIT TO BE | | | PROVIDED WITH AN AUXILIARY DRAIN PAN, OR AS AN | | | ALTERNATIVE, A FLOAT SWITCH DEVICE WICH WILL SHOT DOWN | | | THE SYSTEM IN CASE OF CONDENSATE STOPPAGE. | | | | | | REVIEWED BY JOHN ARITON. PLEASE CALL HAROLD MOSER AT | | | 561-805-6732 FO ADDITIONAL INFORMATION. |
|