 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN
 WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5;
 505.5.3; T. 505.5.3
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN
 DISCONNECTING MEANS. NEC 110.16, 110.22
  
 VERIFY SAFE WORKING CLEARANCE HAS BEEN PROVIDED AT THE
 PANEL BOARDS AND DISCONNECTS. NEC 110.26
  
 PROVIDE A STRUCTURAL MOUNTING DETAIL FOR ANY
 TRANSFORMERS BEING SUSPENDED BY THE BUILDING STRUCTURE.
 FBC 1604.1
  
 PROVIDE A FIRE STOP DETAIL FOR ALL WALL AND FLOOR
 PENETRATIONS OF FIRE RATED ASSEMBLIES. NEC 300.21
  
 VERIFY THE ELECTRICAL DISCONNECTING MEANS AND PANEL
 BOARDS HAVE A FAULT CURRENT RATING THAT IS SUFFICIENT
 AT NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 PROVIDE SPECIFICATIONS AND LISTING FOR PREWIRED OFFICE
 MODULAR PARTITIONS. NEC 90.7, 605.2
  
 PROVIDE A NOTE ON PLANS REGARDING THE LIMITATIONS OF
 USE FOR MULTI-WIRE BRANCH CIRCUITS. NEC 210.4, 605.8(D)
  
 PROVIDE A NOTE ON PLANS REGARDING THE VOLTAGE
 LIMITATIONS AND SEPARATION WITH BARRIERS REQUIRED FOR
 SWITCHES AND ADJACENT DEVICES. NEC 404.8
  
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR FIRE
 ALARM SYSTEMS, SECURITY, VOICE, AND DATA SYSTEMS
  