| | TENANT BUILD OUT |
| | |
| | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | REVIEW COMMENTS. |
| | |
| | PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN |
| | WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY |
| | CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5; |
| | 505.5.3; T. 505.5.3 |
| | |
| | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION |
| | FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN |
| | DISCONNECTING MEANS. NEC 110.16, 110.22 |
| | |
| | VERIFY SAFE WORKING CLEARANCE HAS BEEN PROVIDED AT THE |
| | PANEL BOARDS AND DISCONNECTS. NEC 110.26 |
| | |
| | PROVIDE A STRUCTURAL MOUNTING DETAIL FOR ANY |
| | TRANSFORMERS BEING SUSPENDED BY THE BUILDING STRUCTURE. |
| | FBC 1604.1 |
| | |
| | PROVIDE A FIRE STOP DETAIL FOR ALL WALL AND FLOOR |
| | PENETRATIONS OF FIRE RATED ASSEMBLIES. NEC 300.21 |
| | |
| | VERIFY THE ELECTRICAL DISCONNECTING MEANS AND PANEL |
| | BOARDS HAVE A FAULT CURRENT RATING THAT IS SUFFICIENT |
| | AT NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. NEC 110.9 |
| | |
| | PROVIDE SPECIFICATIONS AND LISTING FOR PREWIRED OFFICE |
| | MODULAR PARTITIONS. NEC 90.7, 605.2 |
| | |
| | PROVIDE A NOTE ON PLANS REGARDING THE LIMITATIONS OF |
| | USE FOR MULTI-WIRE BRANCH CIRCUITS. NEC 210.4, 605.8(D) |
| | |
| | PROVIDE A NOTE ON PLANS REGARDING THE VOLTAGE |
| | LIMITATIONS AND SEPARATION WITH BARRIERS REQUIRED FOR |
| | SWITCHES AND ADJACENT DEVICES. NEC 404.8 |
| | |
| | |
| | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR FIRE |
| | ALARM SYSTEMS, SECURITY, VOICE, AND DATA SYSTEMS |
| | |