| 2014-08-26 15:17:28 | DATE: 8/18/2014 |
| | PROJECT: CARSON 240 PALMETTO LN |
| | PERMIT#: 14080064 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 3RD ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | DUPLICATE COMMENT: |
| | 1) NEC 310.15(6) |
| | STATES IN PART "FOR APPLICATION OF THIS SECTION, THE |
| | MAIN POWER FEEDER SHALL BE THE FEEDER BETWEEN THE MAIN |
| | DISCONNECT AND THE PANELBOARD THAT SUPPLIES, EITHER BY |
| | BRANCH CIRCUITS OR BY FEEDERS, OR BOTH, ALL LOADS THAT |
| | ARE PART OR ASSOCIATED WITH THE DWELLING UNIT. " |
| | THIS MEANS ONLY ONE SERVICE ENTRANCE OR FEEDER TO ONE |
| | MAIN NOT MORE THAN ONE. THE PURPOSE OF THIS SECTION IS |
| | TO DIVERSIFY THE TOTAL LOAD EVENLY ACCROSS THE |
| | CONDUCTORS WHEN THERE IS MORE THAN ONE MAIN THAT CAN |
| | NOT BE ACCOMPLISHED. THEREFORE A FULL SIZE SERVICE |
| | ENTRANCE AND FEEDER IS REQUIRED. SEE NEC310.16 REVISE |
| | THE RISER DIAGRAM ACCORDINGLY. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT |
| | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| | ITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |