| 2014-08-13 10:21:22 | 6701 NORTH JOG ROAD - MAINTENANCE BUILDING RACK STORAGE | | | PERMIT #14080063 | | | MASTER #12030240 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | A DETAILED NARRATIVE/PLAN IS NEEDED INDICATING THE | | | PROPOSED STORAGE HEIGHTS, COMMODITY CLASSIFICATIONS, | | | STORAGE ARRANGEMENT (PALLETIZED, SOLID PILED, BIN BOX, | | | SHELF), ENCAPSULATED/NON-ENCAPSULATED STORAGE, | | | FLAMMABLE LIQUIDS, HAZARDOUS CHEMICALS, ETC. | | | | | | PROVIDE MEZZANINE DETAILS FOR STAIR, HANDRAILS, AND | | | GUARDRAILS. CLEARLY INDICATE THE LOCATION OF ALL | | | GUARDRAILS. | | | | | | A REVISED LIFE SAFETY PLAN IS NEEDED FOR THE MASTER | | | PERMIT MAINTENANCE BUILDING (#12030240) TO ACCOMODATE | | | FOR THE PROPOSED RACK STORAGE AND MEZZANINE. EXIT | | | SIGNAGE, LIGHTING, FIRE EXTINGUISHER LOCATIONS, FIRE | | | ALARM DEVICES, SPRINKLER TYPES AND LOCATIONS MAY ALL BE | | | AFFECTED. | | | | | | THE SPRINKLER DESIGN (PERMIT #12030242) DOES NOT APPEAR | | | TO BE IN ACCORDANCE WITH NFPA 13 FOR HIGH-PILED STORAGE | | | (+12 FEET). ADDITIONALLY, NO SPRINKLER PROTECTION | | | PROVIDED BELOW MEZZANINE STORAGE. IF SPRINKLER | | | PROTECTION IS NEEDED BELOW THE MEZZANINE, THE STRUCTURE | | | WILL NEED TO SUPPORT THE LOAD OF THE SPRINKLER PIPING | | | PER NFPA 13 (5 X THE WEIGHT OF A WATER FILLED PIPE, | | | PLUS 250 LBS). | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|