| 2014-11-22 11:22:28 | BUILDING PLAN REVIEW |
| | PERMIT: 14080059 |
| | ADD: 5660 N MILITARY TRL. |
| | CONT: TBD |
| | TEL: (901)495-8701 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | NOTE: PLANS WERE SUBMITTED BY MAIL "NO PERMIT |
| | APPLICATION WAS PROVIDED", SUBMITTED AS A TBD" TO BE |
| | DETERMINED" BEFORE PERMIT ISSUANCE A QUALIFIED |
| | CONTRACTOR WILL NEED TO SUBMIT A SIGNED AND NOTIRIZED |
| | PERMIT APPLICATION BY THE OWNER AS WELL AS THE |
| | CONTRACTOR. |
| | |
| | 2ND REVIEW |
| | DATE: SAT. NOV. 22/2014 |
| | ACTION: DENIED |
| | |
| | |
| | NOTICE:!!!!!!!!!!!!!!!! |
| | CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES THAT A |
| | LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR TIMES THE |
| | FEE FOR |
| | PLAN REVIEW, IF PLANS ARE REJECTED (3) OR MORE TIMES |
| | FOR REPEATED FAILURE TO CORRECT A CODE VIOLATION. |
| | |
| | 1)COMPLIED. SITE PLAN. |
| | |
| | 2) 2ND REQUEST. THE SUBMITTED SOILS REPORTS ARE COPIES |
| | OF ORIGINAL SOILS REPORTS. THE REPORT HAS A COPIED |
| | ENGINEERS SIGNATURE, & NO SEAL. |
| | |
| | 61G15-23.002(1) SEAL, SIGNATURE AND DATE SHALL BE |
| | AFFIXED. A PROFESSIONAL ENGINEER SHALL SIGN HIS NAME |
| | AND AFFIX HIS SEAL TO ALL PLANS, SPECIFICATIONS, |
| | REPORTS, FINAL BID DOCUMENTS PROVIDED TO THE OWNER OR |
| | THE OWNER?S REPRESENTATIVE, OR OTHER DOCUMENTS PREPARED |
| | OR ISSUED BY SAID REGISTRANT AND BEING FILED FOR PUBLIC |
| | RECORD. THE DATE THAT THE SIGNATURE AND SEAL IS AFFIXED |
| | AS PROVIDED HEREIN SHALL BE ENTERED ON SAID PLANS, |
| | SPECIFICATIONS, REPORTS, OR OTHER DOCUMENTS IMMEDIATELY |
| | UNDER THE SIGNATURE OF THE PROFESSIONAL ENGINEER. |
| | |
| | MISSING SOILS REPORT 2010 FBC-B 1803.2 INVESTIGATIONS |
| | REQUIRED. GEOTECHNICAL INVESTIGATIONS SHALL BE |
| | CONDUCTED IN ACCORDANCE WITH SECTIONS 1803.3 THROUGH |
| | 1803.5. |
| | 1803.3 BASIS OF INVESTIGATION. SOIL CLASSIFICATION |
| | SHALL BE BASED ON OBSERVATION AND ANY NECESSARY TESTS |
| | OF THE MATERIALS DISCLOSED BY BORINGS, TEST PITS OR |
| | OTHER SUBSURFACE EXPLORATION MADE IN APPROPRIATE |
| | LOCATIONS. ADDITIONAL STUDIES SHALL BE MADE AS |
| | NECESSARY TO EVALUATE SLOPE STABILITY, SOIL STRENGTH, |
| | POSITION AND ADEQUACY OF LOAD-BEARING SOILS, THE EFFECT |
| | OF MOISTURE VARIATION ON SOIL-BEARING CAPACITY, |
| | COMPRESSIBILITY, LIQUEFACTION AND EXPANSIVENESS. |
| | |
| | 3) PARTIAL APPROVED. THE DESIGNER OF RECORD HAS |
| | REQUESTED THE MISSING PRODUCT APPROVALS TO COME IN |
| | AFTER PERMIT ISSUANCE AS DEFERRED SUBMITTALS. THE |
| | COVERSHEET A0 LIST THE PRODUCT APPROVALS, WE REQUIRE |
| | THE PRODUCT APPROVALS 2 COPIES OF EACH ON E FOR RECORD |
| | RETENION THE OTHER FOR THE FIELD INSPECTORS. |
| | WINDOWS AND DOORS WITH GLAZING, IDENTIFY WHICH MODEL IF |
| | MORETHAN ONE TYPE IS LISTED (FL REPORTS), IDENTIFY THE |
| | TYPE OF GLAZING TO BE INSTALLED, INDENTIFY WIDTH & |
| | LENGTH OF GLAZING UNITS, MULLIONS, AND ASSOCIATED |
| | PRESSURES. ETC. 2010 FBC-B 1609.1.2 PROTECTION OF |
| | OPENINGS, 1609.6.4.41 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. MISSING YKK FL 16554-R2 |
| | (B) WINDOWS FIXED FL. 16314-R1 / STOREFRONT FL 14218-R2 |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES GAF NOA 12-1218.04 |
| | TO BE SUBMITTED AS A DERRED SUBMITTAL |
| | |
| | 4) DEFERRED SUBMITTALS. 2010 FBC 107.3.4.1 PRODUCT |
| | APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| | DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| | |
| | 5) DEFERRED SUBMITTAL: 107.2.1.2 FOR ROOF ASSEMBLIES |
| | REQUIRED BY THE CODE, THE CONSTRUCTION DOCUMENTS SHALL |
| | ILLUSTRATE, DESCRIBE AND DELINEATE THE TYPE OF ROOFING |
| | SYSTEM, MATERIALS, FASTENING REQUIREMENTS, FLASHING |
| | REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE |
| | REQUIRED TO BE INSTALLED. PRODUCT EVALUATION AND |
| | INSTALLATION SHALL INDICATE COMPLIANCE WITH THE WIND |
| | CRITERIA REQUIRED FOR THE SPECIFIC SITE OR A STATEMENT |
| | BY AN ARCHITECT OR ENGINEER FOR THE SPECIFIC SITE MUST |
| | BE SUBMITTED WITH THE CONSTRUCTION DOCUMENTS. |
| | |
| | 6) DEFERRED SUBMITTAL. PLEASE PROVIDE THE EFIS |
| | MANUAFACTURERS SPECIFICATIONS FOR INSTALATION. 107.2.4 |
| | EXTERIOR WALL ENVELOPE. CONSTRUCTION DOCUMENTS FOR ALL |
| | BUILDINGS SHALL DESCRIBE THE EXTERIOR WALL ENVELOPE IN |
| | SUFFICIENT DETAIL TO DETERMINE COMPLIANCE WITH THIS |
| | CODE. THE CONSTRUCTION DOCUMENTS SHALL PROVIDE DETAILS |
| | OF THE EXTERIOR WALL ENVELOPE AS REQUIRED, INCLUDING |
| | FLASHING, INTERSECTIONS WITH DISSIMILAR MATERIALS, |
| | CORNERS, END DETAILS, CONTROL JOINTS, INTERSECTIONS AT |
| | ROOF, EAVES OR PARAPETS, MEANS OF DRAINAGE, |
| | WATER-RESISTIVE MEMBRANE AND DETAILS AROUND OPENINGS. |
| | THE CONSTRUCTION DOCUMENTS SHALL INCLUDE MANUFACTURER?S |
| | INSTALLATION INSTRUCTIONS THAT PROVIDE SUPPORTING |
| | DOCUMENTATION THAT THE PROPOSED PENETRATION AND OPENING |
| | DETAILS DESCRIBED IN THE CONSTRUCTION DOCUMENTS |
| | MAINTAIN THE WEATHER RESISTANCE OF THE EXTERIOR WALL |
| | ENVELOPE. THE SUPPORTING DOCUMENTATION SHALL FULLY |
| | DESCRIBE THE WALL SYSTEM WHICH WAS TESTED, WHERE |
| | APPLICABLE, AS WELL AS THE TEST PROCEDURE USED. |
| | |
| | 7) DEFERRED SUBMITTAL. SHEET A3 DETAIL # 1 AS WELL AS |
| | THE ENERGY CALCS INDICATE THE USE OF R-30 INSULATION, |
| | PLEASE PROVIDE A CROSS SECTION OF ROOF WITH THE THE |
| | R-30 INSULATION, THE TYPE OF MATERIAIL ANAD HOW IT WILL |
| | BE ATTACHED TO THE ROOF DECK. ENERGY CODE WHOLE |
| | BUILDING METHOD 506.3.1./ COMPONENTS & CLADDING |
| | 1609.1.2. |
| | |
| | 8) COMPLIED. SHEET S2 DETAIL #4. |
| | |
| | 9) COMPLIED. |
| | |
| | 10) COMPLIED. |
| | |
| | 11) COMPLIED. P. B. C. IMPACT FEE ASSESSMANT. |
| | |
| | 12) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |