| 2014-08-16 08:57:24 | PLAN DENIED | | | | | | 1) REFER TO SECTION 606.2.1 SUPPLY AIR | | | AND SECTION 606.4.1 SUPERVISION.2010 | | | FBC (M) | | | 2) REFER TO SECTION 606.3 INSTALLATION. | | | 2010 FBC (M) | | | 3) PROVIDE A DETAIL FROM THE ENGINEER | | | ON THE CURB TO ROOF TIE DOWN AND RTU | | | TO CURB TIE DOWN. PER SECTION | | | 301.12 WIND RESISTANCE 2010 FBC (M) | | | 4) REFER TO SECTION 1509.7 MECHANICAL UNIT'S | | | 2010 FBC. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|