| | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | REVIEW COMMENTS. |
| | |
| | PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN |
| | WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY |
| | CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5; |
| | 505.5.3; T. 505.5.3 |
| | |
| | CONFIRM THAT THE INTERIOR AND EXTERIOR LIGHTING |
| | CONTROLS PROVIDED FUNCTION IN ACCORDANCE WITH THE |
| | FLORIDA ENERGY CODE. EXTERIOR AUTOMATIC CONTROLS SHALL |
| | BE CAPABLE OF RETAINING PROGRAMMING AND THE TIME |
| | SETTING DURING LOSS OF POWER FOR A PERIOD OF AT LEAST |
| | 10 HOURS. FBC ENERGY CONSERVATION 505.2 |
| | |
| | PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION |
| | FOR THE ELECTRIC SERVICE, PANEL BOARDS AND MAIN |
| | DISCONNECTING MEANS. NEC 110.16, 110.22 |
| | |
| | SHOW THE PROPOSED LOCATION OF THE ELECTRICAL SERVICE. |
| | VERIFY SAFE WORKING CLEARANCE HAS BEEN PROVIDED AT THE |
| | SERVICE, PANEL BOARDS AND DISCONNECTS. NEC 110.26, |
| | 240.24(D) |
| | |
| | VERIFY THE ELECTRICAL DISCONNECTING MEANS AND PANEL |
| | BOARDS HAVE A FAULT CURRENT RATING THAT IS SUFFICIENT |
| | AT NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. INDICATE THE MAXIMUM AVAILABLE FAULT |
| | CURRENT AT THE SERVICE POINT OF THE ELECTRICAL UTILITY. |
| | NEC 110.9, 110.10 |
| | |
| | PROVIDE DIMENSIONS AND LISTING FOR THE ELECTRICAL |
| | SERVICE WIREWAY. NEC 110-26, 314.28 |
| | |
| | THE ELECTRIC WATER COOLER REQUIRES GFCI PROTECTION. NEC |
| | 422.52 |
| | |
| | THE DRINK MACHINE REQUIRES GFCI PROTECTION. NEC 422.51 |
| | |
| | |
| | NOTE: A SEPARATE PERMIT AND PLANS ARE REQUIRED FOR FIRE |
| | ALARM SYSTEMS, VIDEO, SECURITY, VOICE, POS, SITE |
| | LIGHTING, SIGNS AND DATA SYSTEMS |
| | |
| | |