| 2014-08-14 08:10:08 | DATE: 8/11/2014 |
| | PROJECT: TESH RESIDENCE |
| | PERMIT#: 14050296 REVISION#14080058 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW ON REVISION |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE A PANEL SCHEDULE TO INDICATE NEW AND |
| | EXISTING LOADS. |
| | 2) PROVIDE A LOAD CALCULATION TO INDICATE EXISTING |
| | ELECTRICAL PANEL AND SERVICE ARE ADAQUATE TO SERVE |
| | ADDITIONAL LOADS. |
| | 3) INDICATE CIRCUITRY ON PLANS. IDENTIFY NEW AND |
| | EXISTING CIRCUITS AND DEVICES. FBC 107.2.1. |
| | 4) PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE |
| | BATHROOMS. NEC 210.11 (C)(3) |
| | 5) INDICATE STAIRWAY AND LANDINGS FROM 1ST TO 2ND FL. |
| | 6) INCATE FAN BOXES WHERE REQUIRED FOR SUPPORT OF A |
| | CEILING FAN. NEC 314.27(A) |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT |
| | /WP-CONTENT/UPLOADS/SITES/33/2013/09/APPLICATION_RESUBM |
| | ITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |