| Plan Review Notes For Permit 14080035 |
| Permit Number |
14080035 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2014-11-24 18:41:10 | MECHANICAL REVIEW APPROVED WITH PROVISO: | | | 1-PROVIDE EQUIPMENT SIZING CALCULATIONS BASED ON THE | | | ACTUAL BUILDING ORIENTATION OF THIS LOT. AS REQUIRED BY | | | SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION. | | | CALCULATIONS SUBMITTED AND EQUIPMENT LISTED IN THE A/C | | | PLAN SUBMITTED ARE DONE FOR WORST CASE SCENARIO. REVISE | | | AS REQUIRED. | | | | | | 2- A/C PLAN SUBMITTED NEEDS THE NAME AND SIGNATURE OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN AS REQUIRED BY | | | SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
|