| Plan Review Notes For Permit 14080035 |
| Permit Number |
14080035 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2014-11-24 18:36:21 | BUILDING REVIEW APPROVED WITH PROVISO: | | | | | | 1- WINDOWS/DOORS WITH GLAZING: PROVIDE MANUFACTURER'S | | | SPECIFICATIONS SHOWING THE U-FACTOR AND SHGC FACTOR | | | SPECIFIED ON THE ENERGY CALCULATIONS IN ITEM #7. | | | 2- ENERGY CALCULATIONS: REVISE THE DOOR TYPE ON PAGE 3 | | | OF 6. THERE ARE NOT WOOD DOORS. | | | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR: | | | A) TYPE OF "STICKY BACK" ROOF UNDERLAYMENT AS SPECIFIED | | | ON PLANS. | | | B) ROOF TILE ADHESIVE RTA-1 NOA 12-0228.18 SUBMITTED: | | | INSTALLATION NOTE #1 INDICATES THAT MAY BE USED WITH | | | ROOF TILE THAT LISTS THE ATTACHMENT RESISTANCE VALUES | | | USING THIS PRODUCT. ROOF TILE NOA 11-0510.02 SUBMITTED | | | DOESN'T LIST THIS ADHESIVE. UNABLE TO VERIFY THE | | | ADHESIVE RESISTANCE VALUE. PROVIDE INFORMATION THAT | | | SHOWS THE RESISTANCE VALUE OF THE RTA-1. | | | C) 6'-0" WIDE OVERHEAD GARAGE DOOR AS SPECIFIED ON | | | PLANS. | | | D) PRECAST LINTELS. NOA 12-0209.13 SUBMITTED WAS | | | SUPERSEDED BY MIAMI-DADE. NEED CURRENT NOA. | | | 4- A) DESIGNER OF RECORD TO REVIEW AND APPROVE IN | | | WRITING ALL PRODUCT APPROVALS. | | | B) PLEASE PLACE PRODUCT APPROVAL REVIEW STAMP ON THE | | | FRONT OF THE PRODUCT APPROVAL NOT ON THE BACK OF THE | | | SHEET. |
|