Plan Review Notes
Plan Review Notes For Permit 14080035
Permit Number 14080035
Review Stop B
Sequence Number 3
Notes
Date Text
2014-11-24 18:36:21BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- WINDOWS/DOORS WITH GLAZING: PROVIDE MANUFACTURER'S
 SPECIFICATIONS SHOWING THE U-FACTOR AND SHGC FACTOR
 SPECIFIED ON THE ENERGY CALCULATIONS IN ITEM #7.
 2- ENERGY CALCULATIONS: REVISE THE DOOR TYPE ON PAGE 3
 OF 6. THERE ARE NOT WOOD DOORS.
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR:
 A) TYPE OF "STICKY BACK" ROOF UNDERLAYMENT AS SPECIFIED
 ON PLANS.
 B) ROOF TILE ADHESIVE RTA-1 NOA 12-0228.18 SUBMITTED:
 INSTALLATION NOTE #1 INDICATES THAT MAY BE USED WITH
 ROOF TILE THAT LISTS THE ATTACHMENT RESISTANCE VALUES
 USING THIS PRODUCT. ROOF TILE NOA 11-0510.02 SUBMITTED
 DOESN'T LIST THIS ADHESIVE. UNABLE TO VERIFY THE
 ADHESIVE RESISTANCE VALUE. PROVIDE INFORMATION THAT
 SHOWS THE RESISTANCE VALUE OF THE RTA-1.
 C) 6'-0" WIDE OVERHEAD GARAGE DOOR AS SPECIFIED ON
 PLANS.
 D) PRECAST LINTELS. NOA 12-0209.13 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. NEED CURRENT NOA.
 4- A) DESIGNER OF RECORD TO REVIEW AND APPROVE IN
 WRITING ALL PRODUCT APPROVALS.
 B) PLEASE PLACE PRODUCT APPROVAL REVIEW STAMP ON THE
 FRONT OF THE PRODUCT APPROVAL NOT ON THE BACK OF THE
 SHEET.