2014-11-17 16:02:53NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS BASED ON THE
 ACTUAL BUILDING ORIENTATION OF THIS LOT. AS REQUIRED BY
 SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION.
 CALCULATIONS SUBMITTED AND EQUIPMENT LISTED IN THE A/C
 PLAN SUBMITTED ARE DONE FOR WORST CASE SCENARIO. REVISE
 AS REQUIRED.
  
 2- A/C PLAN SUBMITTED NEEDS THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN AS REQUIRED BY
 SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  