| 2015-01-21 08:30:46 | PLAN REVIEW COMMENTS |
| | |
| | |
| | 4TH REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | MECHANICAL |
| | |
| | 1) (REPEAT COMMENT) THE LOAD CALCULATION AND ENERGY |
| | FORM IS FOR TWO (2) SYSTEMS AND THE PLANS SPECIFY THREE |
| | (3) SYSTEMS. PLEASE CORRECT. FBC 107.2.1 & FBC ENERGY |
| | CONSERVATION 403.6.1.1 AND FBC 107.1.2 |
| | |
| | 2) THE MECHANICAL PLANS SPECIFY THREE (3) A/C UNITS. |
| | TWO (2) 27,400 BTU/HR UNITS WITH 13.5 SEER AND ONE (1) |
| | 17,800 BTU/HR UNIT WITH 14.5 SEER ARE SPECIFIED. THE |
| | ENERGY FORM 405-10 LISTS TWO (2) UNITS. ONE (1) 27,400 |
| | BTU/HR WITH 13.5 SEER AND ONE (1) 34,000 BTU/HR WITH |
| | 13.5 SEER ARE LISTED. THE LOAD CALCULATIONS LIST THE |
| | SAME TWO (2) UNITS AS THE WORST CASE ENERGY FORM |
| | 405-10. PROVIDE THE LOAD CALCULATIONS FOR THE NORTEAST |
| | ORIENTATION OF THE THE BUILDING AS SHOWN ON THE SURVEY |
| | AND THE MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR |
| | AND INDOOR UNITS WITH THE SENSIBLE AND TOTAL COOLING |
| | CAPACITIES AT THE DESIGN CONDITIONS AS REQUIRED BY FBC |
| | ENERGY CONSERVATION SECTION 403.6 HEATING AND COOLING |
| | EQUIPMENT (MANDATORY). |
| | 403.6.1 EQUIPMENT SIZING. |
| | HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN |
| | ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT |
| | LOADS CALCULATED IN ACCORDANCE WITH MANUAL J OR OTHER |
| | APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES, |
| | BASED ON BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION |
| | OF THE BUILDING. THE MANUFACTURER AND MODEL NUMBER OF |
| | THE OUTDOOR AND INDOOR UNITS (IF SPLIT SYSTEM) SHALL BE |
| | SUBMITTED ALONG WITH THE SENSIBLE AND TOTAL COOLING |
| | CAPACITIES AT THE DESIGN CONDITIONS DESCRIBED IN |
| | SECTION 302.1. THIS CODE DOES NOT ALLOW DESIGNER SAFETY |
| | FACTORS, PROVISIONS FOR FUTURE EXPANSION OR OTHER |
| | FACTORS WHICH AFFECT EQUIPMENT SIZING. SYSTEM SIZING |
| | CALCULATIONS SHALL NOT INCLUDE LOADS CREATED BY LOCAL |
| | INTERMITTENT MECHANICAL VENTILATION SUCH AS STANDARD |
| | KITCHEN AND BATHROOM EXHAUST SYSTEMS. |
| | |
| | |
| | |
| | |