| Plan Review Notes For Permit 14080028 |
| Permit Number |
14080028 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2014-12-23 19:08:04 | PLAN REVIEW COMMENTS | | | | | | | | | 3RD REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | MECHANICAL | | | | | | 1) ( 2ND REPEAT COMMENT ) FBC 107.2.1 - INFORMATION ON | | | CONSTRUCTION DOCUMENTS. ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE | | | DESIGN. ( REPEAT COMMENT ) THERE IS NO SIGNATURE ON THE | | | MECHANICAL PLANS AT ALL, ELECTRONIC, DIGITAL OR OTHER | | | AS STATED IN YOUR LETTER. SEE FLORIDA STATUTES CHAPTER | | | 668 REGUARDING THE USE OF ELECTRONIC COMMERCE, | | | ELECTRONIC SIGNATURES AND DIGITAL SIGNATURES. | | | | | | 2) THE SURVEY THAT WAS SUBMITTED IS INCORRECT. ON SHEET | | | 1 OF THE SURVEY THE FRONT DOOR FACES NORTHEAST AND ON | | | SHEET 2 IT FACES EAST. SUBMIT A CORRECTED SURVEY. FBC | | | 107.2.1 | | | | | | 3) THE LOAD CALCULATION IS FOR TWO (2) SYSTEMS AND THE | | | PLANS SPECIFY THREE (3) SYSTEMS. PLEASE CORRECT. FBC | | | 107.2.1 & FBC ENERGY CONSERVATION 403.6.1.1 | | | | | | 4) THE WHOLE BUILDING LOAD FOR AN EAST ORIENTATION IS | | | 4.74 TONS AND FOR NORTHEAST IT IS 4.63 TONS. THE TOTAL | | | FOR THE EQUIPMENT ON THE MECHANICAL PLAN IS 6.05 TONS. | | | PER FBC ENERGY CONSERVATION 403.6.1.1 THE EQUIPMENT | | | SHOULD TOTAL 5 TONS. | | | | | | |
|