| 2014-11-14 18:19:11 | PLAN REVIEW COMMENTS |
| | |
| | 2ND REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | BUILDING |
| | |
| | 1) SUBMIT TWO SETS OF ENERGY CALCULATIONS THAT |
| | ADEQUATELY REPRESENT THE STRUCTURE AND ITS COMPONENTS. |
| | SEE COMMENTS #1 & #6 FROM 1ST REVIEW. FBC ENERGY |
| | CONSERVATION SECT. 103.2.2 |
| | |
| | 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| | THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD. SPECIFICALLY. |
| | A) "STICKY BACK" ROOF TILE UNDERLAYMENT AS SPECIFIED ON |
| | THE PLANS. |
| | B) THE 6' X 8' OVERHEAD GARAGE DOOR. |
| | C) THE PRODUCT APPROVAL FOR THE 3M, AH-160 FOAM ROOF |
| | TILE ADHESIVE THAT HAD BEEN SUPERSEDED WAS REPLACED |
| | WITH PRODUCT APPROVALS FOR 3M, RTA-1 (NOA 12-0228.18). |
| | THE INSTALLATION NOTES REQUIRE THIS PRODUCT TO BE USED |
| | WITH APPROVED ROOF TILES THAT LIST IT AS A METHOD OF |
| | ATTACHMENT WITH A SPECIFIED MINIMUM ATTACHMENT |
| | RESISTANCE. THE PRODUCT APPROVAL FOR THE ROOF TILE THAT |
| | WAS SUBMITTED DOES NOT LIST THIS PRODUCT. FBC-R 301.1 |
| | |
| | 3) ONE SET OF THE TRUSS DRAWINGS IS MISSING FROM THE |
| | SUBMITTAL. FBC107.1 GENERAL. SUBMITTAL DOCUMENTS |
| | CONSISTING OF CONSTRUCTION DOCUMENTS, STATEMENT OF |
| | SPECIAL INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA |
| | SHALL BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT |
| | APPLICATION. |
| | |
| | IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE |
| | CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER |
| | INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN |
| | ADDRESSED. |
| | |
| | |
| | |
| | |