| Plan Review Notes For Permit 14080028 |
| Permit Number |
14080028 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-08-29 16:02:25 | 2010 FBC | | | | | | GAS REVIEW DENIED | | | | | | 1) SPECIFY THE LENGTH AND SIZE OF EACH SECTION OF PIPE | | | ON THE GAS ISOMETRIC DRAWING. CITY AMENDMENTS 107.2.1 & | | | 2010 FBC FUEL GAS | | | | | | 2) SPECIFY THE 2010 FBC FUEL GAS AS THE APPLICABLE CODE | | | IN THE NOTES, RATHER THAN THE LATEST GAS CODE. CITY | | | AMENDMENTS 107.2.1 & FBCR CHAPTER 43. | | | | | | 3) THE TOTAL DEVELOPED LENGTH FROM THE METER TO THE | | | MOST REMOTE OUTLET IS INCONSISTENT. IT IS 84 L.F. ONE | | | PLACE AND 92 L.F. IN ANOTHER. CITY AMENDMENTS 107.2.1 & | | | 2010 FBCR APPENDIX A - USE OF CAPACITY SECTION A.3.1(4) | | | | | | 4) THE TOTAL BTUH LOAD IS SPECIFIED AS 265,000 BTUH, | | | HOWEVER THE TOTAL OF THE INDIVIDUAL APPLIANCE BTUH | | | LOADS ARE DIFFERENT. PLEASE CORRECT. | | | | | | 5) IF THE VOLUME OF GAS FOR THE APPLIANCE | | | (MANUFACTURER'S INPUT RATING) IS NOT KNOWN AT THE TIME | | | OF SUBMITTAL FOR PERMIT, THE RATING FROM TABLE 402.2 OF | | | THE 2010 FBC FUEL GAS SHALL BE USED. THE BTUH FOR A | | | CLOTHES DRYER IS 35,000 AND THE PLAN HAS 22,000. PLEASE | | | CORRECT. | | | | | | 6) THE PLANS SPECIFY 2-1/2" SHUT OFF VALVES AT THE | | | APPLIANCES WHERE THE PIPE SIZE IS SPECIFIED AS 1". | | | PLEASE CORRECT. | | | | | | 7) THE PLANS HAVE HAVE 160,000 BTUH FOR THE WATER | | | HEATER. THIS APPEARS TO BE HIGH FOR A TANK TYPE WATER | | | HEATER. PLEASE VERIFY. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|