2014-08-29 16:02:252010 FBC
  
 GAS REVIEW DENIED
  
 1) SPECIFY THE LENGTH AND SIZE OF EACH SECTION OF PIPE
 ON THE GAS ISOMETRIC DRAWING. CITY AMENDMENTS 107.2.1 &
 2010 FBC FUEL GAS
  
 2) SPECIFY THE 2010 FBC FUEL GAS AS THE APPLICABLE CODE
 IN THE NOTES, RATHER THAN THE LATEST GAS CODE. CITY
 AMENDMENTS 107.2.1 & FBCR CHAPTER 43.
  
 3) THE TOTAL DEVELOPED LENGTH FROM THE METER TO THE
 MOST REMOTE OUTLET IS INCONSISTENT. IT IS 84 L.F. ONE
 PLACE AND 92 L.F. IN ANOTHER. CITY AMENDMENTS 107.2.1 &
 2010 FBCR APPENDIX A - USE OF CAPACITY SECTION A.3.1(4)
  
 4) THE TOTAL BTUH LOAD IS SPECIFIED AS 265,000 BTUH,
 HOWEVER THE TOTAL OF THE INDIVIDUAL APPLIANCE BTUH
 LOADS ARE DIFFERENT. PLEASE CORRECT.
  
 5) IF THE VOLUME OF GAS FOR THE APPLIANCE
 (MANUFACTURER'S INPUT RATING) IS NOT KNOWN AT THE TIME
 OF SUBMITTAL FOR PERMIT, THE RATING FROM TABLE 402.2 OF
 THE 2010 FBC FUEL GAS SHALL BE USED. THE BTUH FOR A
 CLOTHES DRYER IS 35,000 AND THE PLAN HAS 22,000. PLEASE
 CORRECT.
  
 6) THE PLANS SPECIFY 2-1/2" SHUT OFF VALVES AT THE
 APPLIANCES WHERE THE PIPE SIZE IS SPECIFIED AS 1".
 PLEASE CORRECT.
  
 7) THE PLANS HAVE HAVE 160,000 BTUH FOR THE WATER
 HEATER. THIS APPEARS TO BE HIGH FOR A TANK TYPE WATER
 HEATER. PLEASE VERIFY.
  