| Plan Review Notes For Permit 14080013 |
| Permit Number |
14080013 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-11 09:43:31 | 1)SHOW THE LENGTH DIMENSION OF EACH SECTION OF GAS | | | RISER TO CONFIRM THE TOTAL LONGEST LENGTH FROM THE | | | POINT OF DELIVERY TO THE MOST REMOTE OUTLET. INCLUDE | | | ALL DROPS AND STUB-OUTS. WPB ADMIN. AMEND. TO 2010 FBC | | | SEC. 107.2.1. | | | 2) THE GAS RISER IS SHOWING 2 1/2 " VALVES ON 1" GAS | | | LINES. CLARIFY. | | | 3) I CALCULATED 260,000 BTU'S AND THE GAS LOAD ON THE | | | PLAN STATES 265.000 BTU'S CLARIFY. | | | 4) SHT.A-1-GARAGE-NOTE REFERS TO 2010 FBC SEC. 3034 FOR | | | PROTECTION OF WATER HEATER. THERE IS NO SUCH CODE | | | SECTION IN THE BUILDING CODE OR IN THE RESIDENTIAL | | | CODE. CLARIFY. | | | 5) SHT.A-3-THE GAS NOTES REFER TO AN LP GAS SYSTEM AND | | | ALSO NATURAL GAS AND THE SPECIFIC GRAVITY YOU HAVE | | | LISTED FOR THE TYPE OF GAS IS FOR LP GAS AND A GAS | | | METER AND A CONNECTION TO THE GAS COMPANY IS SHOWN ON | | | THE RISER DIAGRAM. WHAT IS IT, LP OR NATURAL? REMOVE | | | ANY NOTES THAT ARE NOT APPLICABLE TO THE CORRECT TYPE | | | OF GAS. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805- 6692 | | | |
|