Plan Review Notes
Plan Review Notes For Permit 14080004
Permit Number 14080004
Review Stop P
Sequence Number 1
Notes
Date Text
2014-08-31 07:21:33WPB ADMIN. AMEND. TO 2010 FBC 107.2.1.
 1) THE SANITARY RISER DOES NOT CORRELATE WITH THE FLOOR
 PLAN.
 2) THE BTU LOAD FOR THE GAS SYSTEM ON THE PLAN IS
 WRONG. THE LOAD IS 260,000. THE WATER HEATER IS SHOWN
 AS 160,000. THIS SEEMS HIGH. IS IT CORRECT?
 4) SHOW THE LENGTH DIMENSION OF EACH SECTION OF GAS
 RISER TO CONFIRM THE TOTAL LONGEST LENGTH FROM THE
 POINT OF DELIVERY TO THE MOST REMOTE OUTLET. INCLUDE
 ALL DROPS AND STUB-OUTS. WPB ADMIN. AMEND. TO 2010 FBC
 SEC. 107.2.1.
 5) THE GAS RISER IS SHOWING 2 1/2 " VALVES ON 1" GAS
 LINES. CLARIFY.
 7) NOTE ON SHT. A-3 STATES "SEE GAS PLAN AT SHEET E-1."
 THERE IS NO GAS PLAN ON E-1 EXCEPT FOR THE GAS METER
 AND A NOTE THAT STATES" 1 1/4" GAS UP TO ATTIC" AND IT
 SHOWS THE GAS APPLIANCES. CLARIFY.
 8) SHT.A-1-GARAGE-NOTE REFERS TO 2010 FBC SEC. 3034 FOR
 PROTECTION OF WATER HEATER. THERE IS NO SUCH CODE
 SECTION IN THE BUILDING CODE OR IN THE RESIDENTIAL
 CODE. CLARIFY.
 9) SHT.A-3-THE GAS NOTES REFER TO AN LP GAS SYSTEM AND
 ALSO NATURAL GAS AND THE SPECIFIC GRAVITY YOU HAVE
 LISTED FOR THE TYPE OF GAS IS FOR LP GAS AND A GAS
 METER AND A CONNECTION TO THE GAS COMPANY IS SHOWN ON
 THE RISER DIAGRAM. WHAT IS IT, LP OR NATURAL? REMOVE
 ANY NOTES THAT ARE NOT APPLICABLE TO THE CORRECT TYPE
 OF GAS.
 10) PROVISIONS SHALL BE MADE FOR THERMAL EXPANSION
 CONTROL OF THE WATER SUPPLY SYSTEM IN ACCORDANCE WITH
 2010 FBCR SEC. P2903.4 & P2903.4.2.DUE TO THE
 INSTALLATION OF A BACKFLOW PREVENTER FOR THE IRRIGATION
 SYSTEM.
  
  