| Plan Review Notes For Permit 14080004 |
| Permit Number |
14080004 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-09-15 13:03:03 | WPB ADMIN. AMEND. TO 2010 FBC 107.2.1. | | | 1) THE BTU LOAD FOR THE GAS SYSTEM ON THE PLAN IS | | | WRONG. THE LOAD IS 260,000. THE WATER HEATER IS SHOWN | | | AS 160,000. THIS SEEMS HIGH. IS IT CORRECT? | | | 2) SHOW THE LENGTH DIMENSION OF EACH SECTION OF GAS | | | RISER TO CONFIRM THE TOTAL LONGEST LENGTH FROM THE | | | POINT OF DELIVERY TO THE MOST REMOTE OUTLET. INCLUDE | | | ALL DROPS AND STUB-OUTS. WPB ADMIN. AMEND. TO 2010 FBC | | | SEC. 107.2.1. | | | 3) THE GAS RISER IS SHOWING 2 1/2 " VALVES ON 1" GAS | | | LINES. CLARIFY. | | | 4) NOTE ON SHT. A-3 STATES "SEE GAS PLAN AT SHEET E-1." | | | THERE IS NO GAS PLAN ON E-1 EXCEPT FOR THE GAS METER | | | AND A NOTE THAT STATES" 1 1/4" GAS UP TO ATTIC" AND IT | | | SHOWS THE GAS APPLIANCES. CLARIFY. | | | 5) SHT.A-1-GARAGE-NOTE REFERS TO 2010 FBC SEC. 3034 FOR | | | PROTECTION OF WATER HEATER. THERE IS NO SUCH CODE | | | SECTION IN THE BUILDING CODE OR IN THE RESIDENTIAL | | | CODE. CLARIFY. | | | 6) SHT.A-3-THE GAS NOTES REFER TO AN LP GAS SYSTEM AND | | | ALSO NATURAL GAS AND THE SPECIFIC GRAVITY YOU HAVE | | | LISTED FOR THE TYPE OF GAS IS FOR LP GAS AND A GAS | | | METER AND A CONNECTION TO THE GAS COMPANY IS SHOWN ON | | | THE RISER DIAGRAM. WHAT IS IT, LP OR NATURAL? REMOVE | | | ANY NOTES THAT ARE NOT APPLICABLE TO THE CORRECT TYPE | | | OF GAS. | | | |
|