2015-01-21 14:50:54PLAN REVIEW COMMENTS
  
  
 4TH REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 MECHANICAL
  
 1) BASED ON THE SURVEY THAT WAS SUBMITTED, THE FRONT
 DOOR FACES WEST. ACCORDING TO THE LOAD CALCULATION THE
 TOTAL COOLING LOAD IS 3.22 TONS FOR THE WHOLE HOUSE
 WITH A WEST ORIENTATION. SYSTEM 1 HAS A TOTAL COOLING
 LOAD OF 1.56 TONS AND SYSTEM 2 HAS A TOTAL COOLING LOAD
 OF 1.66 TONS. FROM THE CALULATIONS IT APPEARS THAT BOTH
 UNITS SHOULD BE 2 TONS AT MOST. THE PLANS SPECIFY A 2.5
 TON AND A 2 TON. THE 403.6.1.1 COOLING EQUIPMENT
 CAPACITY. COOLING ONLY EQUIPMENT SHALL BE SELECTED SO
 THAT ITS TOTAL CAPACITY IS NOT LESS THAN THE CALCULATED
 TOTAL LOAD BUT NOT MORE THAN 1.15 TIMES GREATER THAN
 THE TOTAL LOAD CALCULATED ACCORDING TO THE PROCEDURE
 SELECTED IN SECTION 403.6, OR THE CLOSEST AVAILABLE
 SIZE PROVIDED BY THE MANUFACTURER'S PRODUCT LINES. THE
 CORRESPONDING LATENT CAPACITY OF THE EQUIPMENT SHALL
 NOT BE LESS THAN THE CALCULATED LATENT LOAD. (
 ACCORDING TO THE LOAD CALCULATIONS A WEST FACING
 BUILDING HAS THE LOWEST REQUIRED LOAD. WHY DO THE PLANS
 SPECIFY EQUIPMENT THAT WAS DETERMINED TO BE WORST
 CASE?)
  
  