| 2014-11-15 07:40:33 | 1)VENT FOR TUB & SHOWER IN MASTER BATH SHALL CONNECT | | | ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE.2010 | | | FBCR SEC.P3104.3. A FLAT DRY VENT AS DRAWN IS NOT | | | PERMITTED BY THE PLUMBING CODE.2ND REQUEST. | | | 2)THERE ARE TWO WET BAR OPTIONS SHOWN ON THE SANITARY | | | RISER BUT ONLY ONE SHOWN ON THE FLOOR PLAN AND IT IS | | | ALSO CROSSED OFF AS AN OPTION ON SHT. A-1. CLARIFY.2ND | | | REQUEST. | | | 3) THE FLOOR PLAN HAS A NOTE" STUB-OUT FOR FUTURE | | | SUMMER KITCHEN" BUT NOTHING IS SHOWN ON THE SANITARY | | | RISER. WPB AMEND TO 2010 FBC SEC.107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|