Plan Review Notes
Plan Review Notes For Permit 14071212
Permit Number 14071212
Review Stop B
Sequence Number 2
Notes
Date Text
2014-11-13 17:13:53PLAN REVIEW COMMENTS
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 BUILDING
  
 1) FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THERE WAS ONLY ONE SET OF ENGINEERED TRUSS
 DRAWINGS IN THE RE-SUBMITTAL PACKAGE.
  
 2) SUBMIT TWO SETS OF ENERGY CALCULATIONS THAT
 ADEQUATELY REPRESENT THE STRUCTURE AND ITS COMPONENTS.
 SEE COMMENTS #1 & #6 FROM 1ST REVIEW. FBC ENERGY
 CONSERVATION SECT. 103.2.2
  
 3) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. SPECIFICALLY.
 A) "STICKY BACK" ROOF TILE UNDERLAYMENT AS SPECIFIED ON
 THE PLANS.
 B) THE 6' X 8' OVERHEAD GARAGE DOOR.
 C) THE PRODUCT APPROVAL FOR THE 3M, AH-160 FOAM ROOF
 TILE ADHESIVE THAT HAD BEEN SUPERSEDED WAS REPLACED
 WITH PRODUCT APPROVALS FOR 3M, RTA-1 (NOA 12-0228.18).
 THE INSTALLATION NOTES REQUIRE THIS PRODUCT TO BE USED
 WITH APPROVED ROOF TILES THAT LIST IT AS A METHOD OF
 ATTACHMENT WITH A SPECIFIED MINIMUM ATTACHMENT
 RESISTANCE. THE PRODUCT APPROVAL FOR THE ROOF TILE THAT
 WAS SUBMITTED DOES NOT LIST THIS PRODUCT. FBC-R 301.1
  
 IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved